As used in this article, the following terms shall have the meanings ascribed in this section:

Dwelling. A building or structure which is wholly or partially used or intended to be used as a residence for one or more persons or family, but does not include recreational vehicles.

Dwelling Unit. A room or group of rooms located within a dwelling and forming a complete and independent habitable unit for a person or a family which includes facilities to be used for living, sleeping, eating, cooking and sanitation.

Hotel. Every building or structure kept, used, or maintained as, and advertised or held out to the public to be, an inn, hotel, motel, family hotel, apartment hotel, lodging house, dormitory, or place where sleeping or rooming accommodations are furnished for hire, or used or maintained for the accommodations of guest, lodgers, or roomers.

Occupant. Any person living, sleeping, cooking, or having actual possession of a dwelling unit, other than a guest, or using the property as a legal address for any purpose; or any person having actual possession of any building or structure other than a dwelling unit or room unit.

Owner. Any person, who along or jointly or severally with others:

(1) Has legal title to any dwelling or dwelling unit, with or without accompanying actual possession thereof; or

(2) Has charge, care, or control of any dwelling or dwelling unit, as owner or agent of the owner, or as executor, administrator, trustee, or guardian of the estate of the owner. Any person thus representing the actual owner shall be bound to comply with the provisions of this article, and of the rules and regulations adopted pursuant to this article, to the same extent as if he or she were the owner.

Person. Any natural person, entity, business, firm, association, partnership, limited partnership, sole proprietorship, corporation, or any group acting as a unit.

Rental property. Any real property containing a rental unit or units.

Rental Unit. Any single unit of a rooming house, dwelling, apartment, or other similar building, excluding hotels which are held for lease or rent.

Rooming Unit. Any dwelling, or that part of any dwelling containing one or more rooming units, in which space is let by the owner or operator to three or more persons who are not husband or wife, son or daughter, mother or father, or sister or brother of the owner or operator.

Smoke detector. A device which detects particles or products of combustion other than heat and emits a loud warning sound or alarm. The smoke detector device shall be equipped with a test button. The smoke detector device may be either batter powered with a minimum nine-volt replaceable power supply, or a non-replaceable, non-removable battery, that can power the smoke alarm for a minimum of 10 years, or powered by 110-volt alternating current with battery backup.

Tenant. Any person living, sleeping, cooking, or having actual possession of a rental dwelling unit, other than a guest, or using the property as a legal address for any purpose; or any person having actual possession of any building or structure other than a dwelling unit or rooming unit.

(a) All residential dwellings shall be equipped with smoke detectors. It is the owner’s responsibility to install approved smoke detectors in rental property.

(b) Smoke detectors shall be installed according to manufacturer’s recommendations in all locations as specified by NFPA 101 Life Safety Code.

(c) If a smoke detector is A.C. powered, it must be directly attached to a junction box not controlled by any switch other than the main power supply and must be battery backed up. The installation of A.C.

powered detectors shall conform to all other electrical standards adopted by the city. A smoke detector required under this Chapter shall be installed according to the directions and specifications of the manufacturer, but not in conflict with any city electrical standards.

(d) The owner is responsible for the installation of the smoke detector as well as:

(1) Replacing non-operational, damaged, or missing smoke detectors.

(2) Replacing smoke detectors that are beyond their life expectancy. (Ten years unless otherwise specified).

(3) Providing all tenants with the manufacturer’s maintenance and testing instructions.

(4) Inspecting and insuring smoke detector is operational prior to new tenant moving in.

(5) Prior to allowing a tenant to move in notifying them of their responsibilities concerning the smoke detectors and the law that prohibits them to destroy or damage a smoke detector or otherwise render inoperable.

(e) No smoke detector may remain in service for more than 10 years unless the manufacturer specifies a different service life.

(f) The tenant shall be responsible for:

(1) Maintaining and testing, in according with the manufacturer’s instructions, smoke alarms that are within the dwelling unit during the term of the tenancy.

(2) Notifying the owner, in writing, if a smoke detector becomes inoperable. Upon receipt of such written notice, the owner shall immediately repair and replace the inoperable alarm(s).

(g) Tampering with smoke detectors is unlawful.

(1) It shall be unlawful for any person to tamper with or remove any smoke detector or its batteries except when it is necessary for maintenance or inspection purpose. Any smoke detector removed for repair or replacement shall be re-installed or replaced so that it is in place with functioning batteries during normal sleeping hours.

(2) At every change of tenant in every rental dwelling unit, smoke detectors shall be tested by the owner, or his or her designee to see that they are in operable condition.

(h) Injunctive relief

(1) In addition to pursuing in the Superior Court for the County of Monroe the penalty of this Chapter, the Chief of the Fire Department, or the Chief Fire Marshal thereof may also bring an action in the name of the city in the Municipal Court or the Superior Court for mandatory or prohibitory injunctive relief to enforce the provisions of this subchapter, including the securing of compliance with any other order of the Chief of the Fire Department or Fire Marshal, and any such action for injunctive relief may be joined with it an action to recover the applicable penalties in this Chapter.

(i) Penalty

(1) Whoever violates any provision of this section shall be fined in accordance with Section 1-14 of this Code. Every day a violation occurs shall constitute a separate offense as prescribed under this section.

(j) Provisions must be made for the hearing impaired in accordance with Title 2 of the Americans with Disabilities Act, NFPA 72, and NFPA Life Safety Code 101.

(k) No dwelling unit or premises may be occupied, used, or rented which does not comply with this section.