Part II - CODE OF ORDINANCES / Chapter 30 - FIRE PREVENTION AND PROTECTION / Article III - FIRE CODE

Sec. 30-62. Exemption.

Sobre este texto

  • As published by Municode, retrieved 2026-11-11
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

(a) Notwithstanding anything in this article, properties located within airports are exempt from article III, chapter 30 of the Code of the City of Jasper as to fire suppression systems. These properties shall be subject to applicable federal and state guidelines including, but not limited to, the Federal Aviation Administration (FAA) guidelines and the Federal Highway Administration (FHWA) guidelines, as applicable.

(b) Notwithstanding the provisions of paragraph (a) herein, hangars at the Pickens County Airport shall be subject to:

(1) Metal buildings constructed as hangars at the Pickens County Airport up to 12,000 square feet are allowed. Hangars up to 12,000 square feet with a door opening 28 feet or less are not required to have sprinkler or foam fire suppression systems unless the hangar use includes hazardous operations, including fuel transfer, welding, torch cutting, torch soldering, doping, and spray painting. Hangars over 12,000 square feet will be reviewed on a case-by-case basis for compliance with FAA criteria and NFPA 409 Standards for hangars.

(2) Hangar square footage is based on the exterior dimensions of the hangar.

Interior partitions to subdivide aircraft storage spaces are not counted as separate structures.

(3) New hangar construction requires the submittal to FAA of Form 7460 Notice of Proposed Construction or Alteration.

(4) Hangars will be constructed at least 50 feet from adjacent hangars; however, hangars may be adjoined if a fire barrier wall with a minimum rating of at least two hours is constructed on each hangar.

(5) Outrigger frames for hangar door openings do not count toward the 50-foot separation between hangars.

(6) When additional enclosed construction is attached to the hangar, such as a shop, office, or shop area, a one-hour fire resistance firewall with openings protected by listed fire doors having a fire resistance of at least 45 minutes will be built between the additional space and the hangar.

(7) Existing hangars at the airport under 3,000 square feet that require relocation as the result of an FAA requirement or related project may be relocated with a ten-foot separation between hangars.

Historia

La línea de historia que la fuente imprime al final de la sección.

(Ord. No. 2024-20, § 1, 8-5-2024)

Reuniones que se refieren a esta sección

Encontradas: 1. Son reuniones de este gobierno cuyas actas o transcripciones automáticas nombran esta sección, o una ordenanza de su línea de historia, de la más reciente a la más antigua. Halladas por regla a partir de las propias palabras de esos registros. Una referencia es un enlace a otro registro, no una afirmación de que la sección se aplica o se cambió.

Leer este código donde se publica (Municode) La fuente es el código de la ciudad tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.

Versión local-code:jasper/code/30-62@2026-11-11-9d8f52aa9c

El asistente puede decir lo que dice esta sección en esta edición, citándola y enlazándola. No aplicará la ley a su situación, y nada de esto es asesoría legal.