Sec. 82-108. Cross connection prohibited.

Sobre este texto

  • As published by Municode, retrieved 2026-11-11
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

(a) No water service connection to any premises shall be installed or maintained by the city unless the water supply is protected as required by state and federal laws and regulations and this division. Service of water to any premises shall be discontinued by the city if a backflow prevention device required by this division and state law is not installed, tested and maintained, or if it is found that a backflow prevention device has been removed or bypassed, or if an unprotected cross connection exists on the premises. Service will not be restored until such conditions or defects are corrected. Applicable requirements for backflow prevention will be complied with, prior to service connection.

(b) When cross connections are found to exist, the owner, his agent, occupant, or tenant will be notified in writing to disconnect the cross connection within the time limit established by the City of Jasper. Degree of protection required and maximum time allowed for compliance will be based upon the potential degree of hazard to the public water supply system. The maximum time limits are as follows:

(1) Cross connections with private wells or other auziliary water supplies - immediate disconnection.

(2) All facilities which pose a health hazard to the potable water system must have a containment assembly in the form of a reduced pressure principle backflow prevention assembly within 60 days.

(3) All industrial and non-residential facilities not identified as a health hazard shall be considered non-health hazard facilities. All non-health hazard facilities must install, as a minimum containment assembly, double check valve assembly within 90 days unless otherwise approved by the City of Jasper.

(4) If, in the judgment of the City of Jasper, an imminent health hazard exists, water service to the building or premises where a cross connection exists may be terminated unless an air gap is immediately provided, or the cross connection is immediately eliminated.

(5) Lawn irrigation systems are required to have a split tap service or designated lawn irrigation service tap. The connection of a lawn irrigation system to the service line at any point after the point of delivery is prohibited.

(6) Based upon recommendation from the City of Jasper, the consumer is responsible for installing sufficient internal isolation backflow prevention assemblies and/or methods in example (air gap, pressure vacuum breakers, reduced pressure principle backflow prevention assembly, double check valve assembly).

(7) Water mains served by the city but not maintained by the City of Jasper should be considered cross connections, with degree of hazard to be determined by the City of Jasper. Degree of protection shall be based upon the degree of hazard, as determined by the City of Jasper.

(8) In the event that a City of Jasper cross connection control inspector does not have sufficient access to every portion of a private water system to allow a complete evaluation of the degree of hazard associated with the particular private water system, as approved reduced pressure principle assembly shall be required as a minimum of protection.

(9) Customers shall not modify their private water system in a manner that would affect the degree of hazard of such system until the City of Jasper has been provided with information showing that the appropriate backflow prevention assembly is installed. If such modification or change determined by the City of Jasper to require the installation of a different backflow prevention assembly, the required backflow prevention assembly must be installed in accordance with provision of this division prior to making the proposed modification or change.

(10) No person shall fill special use tanks or tankers containing pesticides, fertilizers, other toxic chemicals or their residues from the public water system except at a location equipped with an air gap or an approved reduced pressure principle backflow prevention assembly properly installed on the public water supply.

Historia

La línea de historia que la fuente imprime al final de la sección.

(Ord. of 4-7-2014)