Part II - CODE OF ORDINANCES / Chapter 30 - FIRE PREVENTION AND PROTECTION / Article III - FIRE CODE

903.2.1.1. Group A-1

Sobre este texto

  • As published by Municode, retrieved 2026-11-11
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

An automatic sprinkler system shall be provided throughout stories containing Group A-1 occupancy and throughout all stories from the Group A-1 occupancy to and including the levels of exit discharge serving the occupancy

where one of the following conditions exists:

1. The fire area exceeds 12,000 square feet (1115 m2 ).

2. The fire area has an occupant load of 300 or more.

3. The fire area is located on a floor other than a level of exit discharge serving such occupancies.

4. The fire area contains a multiple-theater complex.