Part II - CODE OF ORDINANCES / Chapter 30 - FIRE PREVENTION AND PROTECTION / Article III - FIRE CODE
903.2.1.2. Group A-2.
Sobre este texto
- As published by Municode, retrieved 2026-11-11
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
An automatic sprinkler system shall be provided throughout stories containing Group A-2 occupancies and throughout all stories from the Group A-2 occupancy to and including the levels of exit discharge serving that occupancy
where one of the following conditions exists:
1. The fire area exceeds 4,999 square feet (464.4222 m2 ).
2. The fire area has an occupant load of 100 or more.
3. The fire area is located on a floor other than a level of exit discharge serving such occupancies.