Part III - LAND USE CODE / Chapter 105 - BUILDING REGULATIONS / Article IV - FIRE DISTRICT

Sec. 105-134. Building restrictions.

Sobre este texto

  • As published by Municode, retrieved 2026-11-11
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

(a) Types of construction permitted. Within the fire district every building hereafter erected shall be either Type I, II, III or IV as designated by the International Building Code, except as permitted in section 105-136.

(b) Other specific requirements.

(1) Exterior walls. Exterior walls of buildings located in the fire district shall comply with the requirements in Table 601 within the International Building Code, except as required in subsection (6) of this section.

(2) Group H prohibited. Group H occupancies, as described within the International Building Code, shall be prohibited from location within the fire district.

(3) Construction type. Every building shall be constructed as required based on the type of construction indicated in chapter 6 of the International Building Code.

(4) Roof covering. Roof covering in the fire district shall conform to the requirements of Class A or B roof coverings as defined in section 1505 of the International Building Code.

(5) Structural fire rating.

a. Walls, floors, roofs and their supporting structural members shall be a minimum of one-hour fire-resistance-rated construction.

b. Exceptions.

1. Buildings of Type IV construction.

2. Buildings equipped throughout with an automatic sprinkler system in accordance with section 903.3.1.1. of the International Building Code.

3. Automobile parking structures.

4. Buildings surrounded on all sides by a permanently open space of not less than 30 feet (9144 mm).

5. Partitions complying with section 603.1, item 10 of the International Building Code.

(6) Exterior walls.

a. Exterior load-bearing walls of Type II buildings shall have a fire-resistance rating of two hours or more where such walls are located within 30 feet (9144 millimeters) of a common property line or an assumed property line. Exterior non-load-bearing walls of Type II building located within 30 feet (9144 millimeters) of a common property line or an assumed property line shall have fire resistance ratings as required by Table 601, but not less than one hour. Exterior walls located more than 30 feet (9144 millimeters) from a common property line or an assumed property line shall comply with Table 601.

b. Exception. In the case of one-story buildings that are 2,000 square feet (186 square meters) or less in area, exterior walls located more than 15 feet (4572 millimeters) from a common property line or an assumed property line need only comply with Table 601.

(7) Architectural trim. Architectural trim on buildings located in the fire district shall be constructed of approved noncombustible materials or fire-retardant-treated wood.

(8) Permanent canopies. Permanent canopies over private property are permitted to extend over adjacent open spaces, provided all of the following are met:

a. The canopy and its supports shall be of noncombustible material, fire-retardant-treated wood, Type IV construction or of one-hour fire-resistance-rated construction. Exception:

Any textile covering for the canopy shall be flame-resistant as determined by tests conducted in accordance with NFPA 701 after both accelerated water leaching and accelerated weathering.

b. Any canopy covering, other than textiles, shall have a flame spread index not greater than 25 when tested in accordance with ASTM E 84 or UL 723 in the form intended for use.

c. The canopy shall have at least one long side open.

d. The maximum horizontal width of the canopy shall not exceed 15 feet (4572 millimeters).

e. The fire resistance of exterior walls shall not be reduced.

(9) Roof structures. Structures, except aerial supports 12 feet (3658 millimeters) high or less, flagpoles, water tanks and cooling towers, placed above the roof of any building within the fire district shall be noncombustible material and shall be supported by construction of noncombustible material.

(10) Plastic signs. The use of plastics complying with section 2611 of the International Building Code for signs is permitted provided the structure of the sign in which the plastic is mounted or installed is noncombustible.

(11) Plastic veneer. Exterior plastic veneer is not permitted in the fire district.

Historia

La línea de historia que la fuente imprime al final de la sección.

(Ord. No. 2016-04-19(b), § 1(150.32), 4-19-2016)