Appendix C - ZONING / Article 14 - SUPPLEMENTAL STANDARDS FOR SPECIFIC USES
Section 1448. Utility substation.
Sobre este texto
- As published by Municode, current through 2026-02-03
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
(a) Minimum setbacks. Utility substations, including any required fencing, must be set back a minimum of 60 feet from all public rights-of-way and from adjacent property lines of any lot on which a residence is located, and 30 feet from all other adjacent property lines.
(b) Minimum lot size. The lot on which a utility substation is located must be of sufficient size to meet the minimum setback requirements; however, in no case shall the lot on which a utility substation is located be less than one-quarter acre.
(c) Utility substations, including any woven wire fencing, shall be completely enclosed by decorative fencing such as, but not necessarily limited to, brick, stone or wood. Utility substations must also be enclosed by a woven wire fence at least eight feet high with bottom of fence either flush with the ground or with a masonry footing; however, the requirement for woven wire fencing may be waived if the applicant reasonably demonstrates that the utility substation does not pose a hazard to the public. If the requirement for woven wire fencing is waived, then the zoning administrator may waive the requirement for the building to be completely enclosed by decorative fencing if the zoning administrator determines that such waiver would not negatively impact the aesthetic quality of the building. However, all equipment located outside the building, such as but not limited to generators and tanks, shall be enclosed by decorative fencing.
(d) All outdoor lighting fixtures must be recessed and downcast and shall not produce glare or a nuisance to drivers or the surrounding properties.
(e) No vehicles or equipment may be stored on the lot.
(f) A buffer a minimum of 25 feet wide must be maintained along the side and rear property lines. If any decorative fencing requirements are waived, the zoning administrator may require additional landscaping to preserve the aesthetic quality of the site.
(g) Any building at a utility substation site must be architecturally compatible with adjacent properties.
(h) The applicant must submit a site plan to the administrative officer, showing the proposed location and design of any buildings, the proposed location and type of any exterior equipment, the proposed location and design of all fencing, any proposed landscaping, the means of ingress and egress, the uses of adjacent property, and the distance of all improvements from adjacent property lines and rights-of-way. The site plan must be approved by the administrative officer prior to the issuance of a permit, and the zoning administrator may require any modifications to the site plan necessary to achieve compliance with the standards and spirit of this ordinance.
(i) The development standards in each district shall not apply to utility substations.