(a) Required. Sand and oil or grease interceptors are required as follows:
(1) All users involved in the preparation of food for commercial purposes shall provide oil/grease interceptors or traps. Additionally, any user who generates a wastewater which contains greater than the quantity of oil and grease regulated under sections 114-266 through 114-268, and provided that the excess oil and grease is floatable and can be effectively removed in an oil/grease interceptor or trap, then said user will be required to install a grease/oil interceptor.
(2) All users whose wastewater stream is associated with unusually large quantities or grit, sand or gravel shall be required to install a sand trap. All car/truck wash systems shall be required to install trap design and installation shall be approved by the city.
(3) The requirements of this chapter section shall not apply to private living quarters or dwelling units.
(b) Design criteria. Design criteria shall be as follows:
(1) All sand and oil/grease interceptors used in conjunction with restaurants or other eating establishments shall have a capacity of 15 gallons per seat, except that no grease trap shall be smaller than 750 gallons nor larger than 3,000 gallons.
(2) All sand and oil/grease interceptors used in conjunction with facilities other than eating establishments shall have a capacity that will provide not less than ten minutes nor more than 30 minutes retention time at the peak eight-hour flow rate. Flow-through velocities shall not exceed one foot per second at the peak eight-hour flow rate.
(3) All sand and oil/grease interceptors shall be sized, located and constructed in accordance with the provisions of the duly adopted city plumbing code where such parameters have not been otherwise set forth herein.
(c) Maintenance.
(1) All grease, oil and sand interceptors or traps shall be maintained by the user at his expense, in continuously efficient operation at all times.
(2) In the maintaining of these interceptors, the owner shall be responsible for the proper removal and disposal by appropriate means of the captured material, and shall maintain records of the dates, and means of disposal which are subject to review by the city manager. The frequency of removal shall be such as to ensure that no overflows of oil, grease or sand into the wastewater system ever results.
(d) Proper disposal of collected materials.Any removal and hauling of the collected materials not performed by the owner's employees must be performed by currently licensed waste disposal firms. Under no circumstances shall the collected materials ever be returned to the wastewater system.
Historia
(Ord. No. 2017-0921-01, § 1, 9-21-2017)