Sec. 113-163. Retaining walls.
Sobre este texto
- As published by Municode, retrieved 2026-11-11
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
(1) General requirements.
a. When permanent grades are proposed to be steeper than 2:1 (one vertical foot of rise for every two feet of horizontal displacement) an appropriate retaining
structure shall be designed to reinforce or retain the resulting embankment.
b. An engineered design may be substituted for the reinforced concrete design if approved by the director. All structural components of the wall shall meet the minimum building codes for the proposed use, including provisions for safety railings and fences..
c. All wall designs must demonstrate complete dimensions for line and grade.
Wall design will consider surface and foundation drainage and select backfill material for the proposed conditions.
(2) Permits required. Where retaining walls are to be installed permits shall be obtained in accordance with article VI of these regulations.
(3) Indemnification/certification. For all retaining walls over four feet in height, the owner of the property containing the proposed wall shall complete an owner's indemnification agreement. For all retaining walls over six feet in height, a professional engineer shall design and certify the wall and complete an engineer's certification agreement for each wall permitted.
The following criteria (contained on indemnification/certification agreements) pertain to all walls unless specifically allowed under variance or modification and permission from the appropriate governing authority:
a. Retaining walls must be located three feet outside the public right-of-way;
b. Placement of retaining walls shall comply with any and all applicable easement
restrictions;
c. Retaining walls are to be located within the confines of owner's/applicant's
property; and
d. Retaining walls shall not be located within undisturbed stream buffers and
impervious surface setbacks, floodplains, drainage easements or drainage ways in a manner that impedes the flow of water.
(4) Retaining wall height and materials.
a. All retaining wall structures in excess of six feet shall be designed by a qualified registered professional engineer and
shall be constructed of reinforced concrete, reinforced earth, gabions, or other masonry materials as required by the registered professional engineer.
b. When the necessity for an earth retaining structure is required for a vertical
displacement of six feet or less, appropriate landscaping timbers, or approved equal, may be employed if no permanent structure is supported by the soil retained by the retaining wall. The use of railroad cross ties or other timber product will only be allowed in these
instances when the wall is constructed as per detail.
(5) Handrails. All retaining walls, including stepped or combination wall systems, other than for a stormwater facility, over six feet must have a hand rail or other suitable barrier installed.
See section 13.3.8 for requirements for handrails within the stormwater facilities.
(6) Stepped walls. Embankments in excess of six feet in height that utilize stepped retaining walls shall have the upper wall setback a minimum distance of one times the height of the lower wall or as directed by the registered professional engineer. Grades between the stepped walls shall not exceed 2:1 or as directed by the professional engineer. All stepped walls need to be signed and certified by a registered professional engineer.
(7) Encroachments. Walls shall be located in such a fashion as to not encroach upon existing or proposed drainage easements, drainage courses, buffers or floodplains or to encumber the natural flow of surface runoff of stormwater.
Walls shall be located at a distance from such watercourses to allow for anticipated future maintenance of the easement to prevent a safety hazard to the maintenance workers or to
jeopardize the structural integrity of the wall.
(8) Walls for stormwater facilities (retaining wall permit required). Retaining walls that are proposed for the purpose of a stormwater detention must be designed to demonstrate that the walls are capable of a hydrostatic load as measured from the top of the foundation footing to the highest elevation along the top of the wall.
The hydrological design must allow for a free board dimension of one foot and an emergency overflow capacity equal to the allowable peak discharge for the 100-year storm event. The routing calculations should not take into account the existence of the emergency overflow. Place the overflow device above the projected 100-year flood elevation within the detention area.
Where the walls are located within a fenced stormwater facility no handrails shall be required along the top of the wall.
Where no fencing of the facility has been required and the wall exceeds four feet in height (as measured from top of wall to normal water level or pond bottom for dry facilities), a handrail or other suitable barrier, approved by the director, shall be provided along the top of the wall. The director may require handrails, or other suitable barriers, for wall heights of less than four feet where, in the opinion of the director, conditions exist that pose a safety hazard.
Historia
(Ord. No. 2009-06-18, (13.3), 6-29-2009)