Johns Creek · Ordenanza de zonificación
Appendix A - ZONING / Article XIX - ADMINISTRATIVE PERMITS AND USE PERMITS
19.3.18. Utility Substations (Telephone, Electric, or Gas, etc.).
Sobre este texto
- As published by Municode, retrieved 2026-11-11
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
A. Required Districts: All.
B. Standards:
1. Utility substations measuring less than 35 square feet and less than 5 feet in height from finished grade are exempt from these regulations.
2. All substation structures shall be contained within the boundaries of the subject parcel and meet the minimum development standards of the district unless otherwise required in this article section.
3. Minimum setback of all utility structures from a residential structure shall be:
a. Electric: 200 feet.
b. Gas and Telephone: The applicable minimum setback for the district in which located.
4. A minimum 10-foot wide landscape strip planted to buffer standards shall be required around the perimeter of all utility sites except along lines where buffers are required.
5. For electric substations provide a minimum 50-foot wide replanted or natural buffer adjacent to the property lines of any residential district and/or AG-1 district used for single-family.
6. Interior to landscape strips or buffers that do not accomplish 100% visual screening as defined in the Tree Preservation Ordinance, provide an 8-foot high opaque fence or, masonry wall, a minimum 4-foot high landscaped earthen berm, a vegetative screen or some combination thereof, subject to the approval of the Community Development Department.
Leer este código donde se publica (Municode) La fuente es el código de la ciudad tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.