(a) All public water systemmains shall be a minimum of eight inches in diameter. The pipes to be used for any public water main are as follows:

(1) Ductile iron pipe may be used for all pipe sizes. Such pipe shall be push-on or mechanical joint conforming to AWWA C104, and the interior and exterior shall receive an approved bituminous coating. All gaskets, bolts and lubricants shall be furnished.

(2) Polyvinyl chloride (PVC) pressure pipe may be used for sizes eight through 12 inches for water lines except for fire hydrant branch lines, for creek crossings and 50 feet adjacent thereto or other similar locations. It is the intent that PVC water pipe is to be used in long runs between fittings and/or valves only. PVC pipe shall conform to the requirements of AWWA C-900, Standard for Pressure Pipe With Iron Pipe outside diameter. Pipe shall be class 150 with a standard dimension ration of 18.

(b) Typically, new water mains to be located along any future or existing county roadways shall be placed on the south and west side of the road, set ten feet from the back of the curb or 15 feet from the edge of the pavement where there is no curb. Site specific conditions may vary the actual placement of the water mains. Such variation shall be approved by the manager of development services.

Historia

La línea de historia que la fuente imprime al final de la sección.

(Ord. of 9-18-00(2), § 38-449)