Part II - CODE OF ORDINANCES / Chapter 38 - LAND DEVELOPMENT CODE / Article X - POTABLE WATER REQUIREMENTS / Division 2 - POTABLE WATER SPECIFICATIONS
Sec. 38-459. Water system design criteria.
Sobre este texto
- As published by Municode, current through 2026-06-23
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
(a) Minimum design criteria.
(1) At water main and sewer line crossings, one full length of water pipe (20 feet) must be centered directly over the sewer line such that ten feet of pipe is on each side.
(2) For crossings of new construction of sewer mains and water lines, the water lines are to be on top of sewer mains.
(3) At surface crossing, pipes of special construction with flexible watertight joints must be used.
(4) Only ductile iron is to be used within 20 feet of the bank of any stream.
(b) Locations.
(1) Water main line location. Pipes 16 inches and larger shall have minimum cover of 48 inches and pipes smaller than 16 inches shall have minimum cover of 30 inches. At street intersections or where the new pipelines cross existing or proposed underground lines at the approximate same depth as the new line, the cover shall be increased and the new line laid below the existing or proposed pipelines. Where the new pipeline crosses existing or proposed ditches, the top of pipe shall be a minimum of 36 inches below the existing or proposed invert of ditch, whichever is lower.
(2) Fire hydrant location.
a. The setting of any hydrant shall conform to the following.
1. Curb lines: When placed behind curb, the hydrant barrel shall be set so that no portion of the pumper or hose nozzle cap will be less than 60 inches nor more than 90 inches from the gutter face of the curb.
2. Sidewalk: When set in the lawn space between the curb and the sidewalk or between the sidewalk and the property line, no portion of the hydrant or nozzle cap shall be within 18 inches of the sidewalk.
3. Ditch section streets: When placed along a roadway having a ditch section the hydrant barrel shall be set so that no portion of the pumper or hose nozzle cap will be less than 20 feet nor more than 24 feet from the edge of the roadway pavement.
4. Position of nozzles: All hydrants shall stand plumb and shall have their nozzles parallel with or at right angles to the curb with the pumper nozzle between 18 inches and 24 inches above the ground. Hydrants shall be furnished for a minimum cover of four feet from top of the pipe.
(3) Water service laterals. Water service laterals shall have a minimum cover of 24 inches within the right-of-way. Within five feet of the water meter the cover shall not be reduced to less than 18 inches.
(4) Water meters. Water meters shall be located off of the right-of-way but within six inches of the right-of-way.
(c) Sprinkler connections. For each fire protection sprinkler connection to publicly owned water system, provide a double detector check valve installation consisting of not less than two detector check valves with bypass meter on the second unit and two gate valves all enclosed in an accessible concrete or masonry pit. The pit is to have an aluminum access hatch.
(d) Anchorage of bends, tees, and plugs.
(1) Limiting pipe diameter and degree of bend. Reaction or thrust backing shall be applied on all pipelines four inches in diameter or larger at all tees, plugs, caps and at bends deflecting 22.5 degrees or more according to Table 1 or movement shall be prevented by attaching rust proof tie rods.
(2) Material for reaction backing. Reaction or thrust backing shall be placed between solid ground and the fitting to be anchored. The backing shall be so placed that the pipe and fitting joint will be accessible for repairs.
(3) Retainer glands. Mechanical joint retainer glands of adequate strength to prevent movement or other suitable means my be used instead of concrete backing.
Table 1. Minimum Thrust Block Area Pipe Diameter (inches) Tees, Dead-ends, or 90 Bends 45 Bends 221 /2 Bends 4 1.5 1 None 6 3.0 2.2 1 8 5.5 4.0 1.5 10 8.5 6.0 2.5 12 12 9.0 3 16 22 16 6 18 27 20 8 20 34 24 10 24 48 34 14 30 75 53 21 (Ord. of 9-18-00(2), § 38-459)