(a) Typical fire hydrant spacing shall be 500 feet. Hydrants shall be located in a manner to provide complete accessibility, and in such a manner that the possibility of damage from vehicles or injury to pedestrians will be minimized. Except when waived by the manager of development services, a fire hydrant shall be located at all street intersections in all zoning districts.
(b) Each hydrant shall be connected to the main pipe with a six-inch cast iron or ductile iron branch. Piping between hydrants and mains shall not be plastic. Each fire hydrant shall be controlled by an independent six-inch gate valve. Inlet connection shall be furnished with mechanical joint for connection to spigot of mechanical joint hydrant lead.
(c) Size of hydrant valve shall be 51 /4-inch minimum. All hydrants shall have two, 21 /2-inch hose nozzles and one 41 /2-inch pumper nozzle and shall be designed for 150 pounds working pressure or 300 pounds hydrostatic pressure, and shall conform to the latest specifications of the AWWA C502. All working parts shall be bronze (bronze to bronze waterway). All hose threads shall be national standard threads. On 21
/2-inch outlets, there shall be 60-degree V-threads, 71 /2 threads per inch. On 41 /2-inch pumper nozzles, there shall be four threads per inch. Hydrants shall have a six-inch mechanical joint end inlet.
(d) Fire hydrant main valves shall open against water pressure and close with water pressure.
Operating threads shall be isolated from the hydrant water way completely by an O-ring seal plate.
(e) Hydrants shall be compressive type, self-oiling, non-freezing and provided with a safety flange and coupling. The operating nut shall be totally sealed away from the hydrant barrel and all working parts shall be continuously and automatically lubricated from a large oil reservoir and packing gland. Drain mechanism shall be simple, positive and automatic in operation. The safety flange on the barrel and the safety coupling on the valve stem shall be constructed so as to reduce damage to barrel and stem in case of a traffic accident. The force of impact shall break the flange and spread the coupling. The construction of the flange and coupling shall be such as to permit rapid replacement. They shall be located above the ground line.
(f) The hydrant shall be constructed so as to permit facing the nozzles in any direction at any time without digging or cutting off water. All working parts of the hydrant, including the seat ring shall be removable through the top without digging. Seat rings shall be so shaped and arranged as to be readily removable. Seat rings shall be bronze and shall screw into a bronze bushing in the shoe. Hose and steamer connections shall be breached locked into the hydrant barrel and then caulked with lead to seal them permanently, or threaded and pinned into the hydrant body.