Standard fire hydrants of a type specified by the City of Valdosta in the construction specifications shall be installed as a part of the water distribution system within a subdivision (existing or new) for single-family dwellings. A fire hydrant shall be located at each intersection and additional hydrant or hydrants installed where the distance between intersections exceed 500 feet. In no case shall hydrants be spaced greater than 500 feet and shall have a flow of 750 g.p.m. (gallons per minutes).

In light commercial, apartments, and multifamily dwelling districts, fire hydrants shall be installed so that the distance from fire hydrants to the driveway entrance nearest the front of the building shall not exceed 250 feet, with a total distance not to exceed 500 feet to the extreme back of the building by way of driveways. Hydrants shall have a flow of not less than 750 g.p.m. (gallons per minute) in the following zoning districts: CC, R-15, R-10, R-6, R-6S, R-P, OP, PRD-15, PRD-10, PRD-6. An option, provided automatic sprinklers are installed according to N.F.P.A. regulations, the spacing of hydrants may be increased to 350 feet to the driveway entrance nearest the front of the building, provided the total distance does not exceed 700 feet to the extreme back of the building by way of driveways.

In manufacturing, heavy commercial, industrial and any facility which handles or uses flammable or hazardous materials, hydrants shall be installed within 300 feet to the midpoint of the structure and equally spaced thereafter, not to exceed 300 feet between hydrants and the extreme rear of the building. The distance shall be measured along the line traveled by the fire truck. In the following zoning districts, hydrants shall have a flow capacity of not less than 1,000 g.p.m. (gallons per minutes); CH, M-1, M-2, an option provided automatic sprinklers are installed according to N.F.P.A. requirements, the spacing of hydrants may be increased from 300 feet to 500 feet.

Distance between fire hydrants shall be as specified unless fire department operations would otherwise allow increased spacing. Actual location of fire hydrants shall be the responsibility of the fire chief or his representative.

8-4.3. The entire cost of extending water and sewer lines and their associated services within subdivision shall be borne by the developer.