Plans for all buildings shall indicate how required structural and fire resistance integrity will be maintained where a penetration of a required fire resistance wall, floor or partition will be made for electrical, gas, mechanical, plumbing, signal and communication conduits, pipes and systems and also indicate in sufficient detail how the fire integrity will be maintained where required fire resistance floors intersect the exterior walls. For structures that are also subject to the state fire marshal's inspections (pursuant to state laws and regulations), the plans must be submitted and approved by the state fire marshal's office prior to being submitted to the Bartow County Building Inspections Department. Such requirements are governed by Chapter 2 of Title 25 of the Official Code of Georgia. For informational purposes only, the following summary is provided, but the state law controls this requirement, and O.C.G.A. § 25-2-13(b)(1) should be consulted for full details.
(1) Buildings or structures more than three stories in height;
(2) Buildings with more than 15 sleeping accommodations for hire (hotels, motels, dormitories, etc.);
(3) Schools and academies for any combination of grades 1 to 12 having more than 15 children total enrolled as pupils; all state funded kindergarten programs;
(4) Hospitals, health care centers, mental health facilities, nursing homes, jails, colleges, universities, technical schools, orphanages, convalescent homes providing lodging, personal care or nursing care for more than four persons on a 24-hour basis;
(5) Racetracks, stadiums, grandstands, theaters, and auditoriums; restaurants, bars, lounges, and nightclubs; dance halls and recreation centers; any other place of assembly having an occupant load of more than 300 people (or more than 100 persons if alcohol is served);
(6) Churches having an occupant load of 500 or more persons in a common area or 1,000 or more persons based on total occupant load;
(7) Department stores, shopping centers, and retail shops with more than 25,000 square feet on any one floor (including multi-tenant shopping centers unless separated by walls with two-hour fire resistance);
(8) Group daycare homes and daycare centers required to be licensed by the state and enrolling at least seven children; and
(9) Personal care homes required to be licensed by the state and having at least seven beds.