(a) Inspection and subsequent reports and repairs. The chief of the fire department shall be responsible for the inspection, testing, servicing, painting, documentation of testing and repair of all fire hydrants in the county, such inspection to be made semiannually, and shall file a report concerning the condition of the fire hydrants with the county administrator.
However, if any fire hydrant needs immediate repair, he shall immediately notify the municipally utilities department who shall take immediate action to have the hydrant repaired.
(b) The barrel of fire hydrants shall be set perpendicular to the ground with the lowest discharge at least 15 inches above the finished surface with the large discharge facing the street or closest paved driveway. Hydrants shall be located within six feet of the curb line or at a location suitable to the authority having jurisdiction. The authority having jurisdiction is the fire chief. A cutoff valve shall be installed between the fire hydrant and the main.
Hydrants shall be installed so as the distance between hydrants does not exceed 660 feet of driving distance. Dead end streets and cul-de-sac shall have a fire hydrant installed so that the primary entrance to the most distant building is not greater than 300 feet. When new construction or modification to existing structure is made in areas of existing water mains, and hydrants separation or required fire flow does not meet requirements, construction contractors will be required to install fire hydrants to meet the requirements of this section and the IFC.
(c) All fire hydrants installed within the county boundaries of Brooks County will be three-way hydrants (2) 2.5 discharges and (1) 4.5 discharge (no two-way hydrants). All fire hydrants when installed by the contractor shall be red (industrial enamel pure red) in color.
The bonnets of each hydrant installed shall have a color-coded identifier installed by the fire department to identify hydrant flow.
Historia
(Ord. No. 2022-02(2), Art. VI, 11-7-2022)
Leer este código donde se publica (Municode) La fuente es el código del condado tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.