(a) Water mains and fire hydrants shall be installed under water pressure and ready for firefighting before any sheathing may be installed on walls and roofs of buildings, unless said sheathing is of fire resistive construction.
(b) Hydrants, fittings, valves, and fire department connections shall be of standard and accepted make approved by the county water and fire departments. Fire department connections on the fire hydrant shall be not less than 18 inches or more than 36 inches above the level of the adjoining ground or paving. The thread of such connections shall be uniform with that used by the county fire department.
(c) Hydrants shall meet the requirements of NFPA No. 24, Fire Hydrants for Outside Protection. Hydrants should be placed at least 50 feet from the buildings protected. Where it is impossible to place them at this distance, they may be put nearer, provided they are set in locations where the chance of injury by falling walls is small, and from which personnel are not likely to be driven by smoke or heat while attempting to hookup.
(d) The size and shape of the operating nut, as well as the direction the hydrant stem operates, shall be uniform with hydrants in the county water distribution system specifications.
(e) Additional fire hydrants may be required by the fire department to permit all portions of a development to be reached by hose lays not more than 400 feet by road travel. Three-way hydrants shall be installed in all areas of the county.
Historia
(Ord. of 5-10-2024, (Exh. A, § 12))
Leer este código donde se publica (Municode) La fuente es el código del condado tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.