In all areas of special flood hazard where base flood elevation data have been provided, as set forth in section 46-32 or section 46-53(9), the following provisions are required:
(1) Residential construction. New construction and substantial improvement of any residential structure shall have the lowest floor, including the basement, elevated no lower than two feet above the base flood elevation. Should solid foundation perimeter walls be used to elevate a structure, openings sufficient to facilitate the unimpeded movements of floodwaters shall be provided in accordance with standards of subsection (3).
(2) Nonresidential construction. New construction and substantial improvement of any commercial, industrial, or nonresidential building (or manufactured home) shall have the lowest floor, including the basement, elevated no lower than two feet above the level of the base flood elevation. Buildings located in all A zones may be floodproofed in lieu of being elevated, provided that all areas of the building below the required elevation are watertight, with walls substantially impermeable to the passage of water, and use structural components having the capability of resisting hydrostatic and hydrodynamic loads and the effect of buoyancy. A registered professional engineer or architect shall certify that the standards of this subsection are satisfied. Such certification shall be provided to the official as set forth in section 46-53(7).
(3) Elevated buildings. New construction and substantial improvements of elevated buildings that include fully enclosed areas formed by foundation and other exterior walls below the base flood elevation shall be designed to preclude finished living space and designed to allow for the entry and exit of floodwaters to automatically equalize hydrostatic flood forces on exterior walls.
a. Designs for complying with this requirement must either be certified by a professional engineer or architect or meet the following minimum criteria:
1. Provide a minimum of two openings having a total net area of not less than one square inch for every square foot of enclosed area subject to flooding;
2. The bottom of all openings shall be no higher than one foot above grade;
and
3. Openings may be equipped with screens, louvers, valves or other coverings or devices provided they permit the automatic flow of floodwaters in both directions.
b. Electrical, plumbing, and other utility connections are prohibited below the base flood elevation.
c. Access to the enclosed area shall be the minimum necessary to allow for parking of vehicles (garage door) or limited storage of maintenance equipment used in connection with the premises (standard exterior door) or entry to the living area (stairway or elevator).
d. The interior portion of such enclosed area shall not be partitioned or finished into separate rooms.
(4) Standards for manufactured homes and recreational vehicles. Standards for manufactured homes and recreational vehicles are as follows:
a. All manufactured homes placed or substantially improved on individual lots or parcels, in expansions to existing manufactured home parks or subdivisions, or in substantially improved manufactured home parks or subdivisions, must meet all the requirements for new construction, including elevation and anchoring.
b. All manufactured homes placed or substantially improved in an existing manufactured home park or subdivision must be elevated so that:
1. The lowest floor of the manufactured home is elevated no lower than two feet above the level of the base flood elevation.
2. The manufactured home chassis is supported by reinforced piers or other foundation elements of at least an equivalent strength of no less than 36 inches in height above grade.
3. The manufactured home must be securely anchored to the adequately anchored foundation system to resist flotation, collapse and lateral movement.
4. In an existing manufactured home park or subdivision on which a manufactured home has incurred substantial damage as the result of a flood, any manufactured home placed or substantially improved must meet the standards of subsections (4)b.1 and (4)b.3.
c. All recreational vehicles placed on sites must either.
1. Be fully licensed and ready for highway use; or
2. The recreational vehicle must meet all the requirements for new construction, including the anchoring and elevation requirements of subsections (4)a.1 or (4)b.1.
A recreational vehicle is ready for highway use if it is on its wheels or jacking system, is attached to the site only by quick disconnect type utilities and security devices and has no permanently attached structures.
(5) Floodways. Located within areas of special flood hazard established in section 46-32 are areas designated as floodways. Since the floodway is an extremely hazardous area due to the velocity of floodwaters which carry debris, potential projectiles and has erosion potential, the following provisions shall apply:
a. Prohibit encroachments, including fill, new construction, substantial improvements and other developments unless certification, with supporting technical data, by a registered professional engineer is provided demonstrating that encroachments shall not result in any increase in flood levels during occurrence of the base flood discharge.
b. If subsection (5)a. is satisfied, all new construction and substantial improvements shall comply with all applicable flood hazard reduction provisions of this division.
c. Prohibit the placement of manufactured homes (mobile homes), except in an existing manufactured homes (mobile homes) park or subdivision. A replacement manufactured home may be placed on a lot in an existing manufactured home park or subdivision provided the anchoring standards of section 46-66(2), and the elevation standards of subsection (1) and the encroachment standards of subsection (5)a. are met.
Historia
(Ord. of 10-25-90, art. 5, § B; Ord. of 5-3-16(1))
Leer este código donde se publica (Municode) La fuente es el código del condado tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.