Sec. 54-101. Fire alarm requirements.

Sobre este texto

  • As published by Municode, current through 2025-11-20
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

(a) All fire alarm systems and monitoring stations shall be in compliance with NFPA 72.

(b) With the exception of premises covered by a fire alarm action plan, fire alarm systems shall automatically call 911 upon activation of a fire alarm (prior to the investigation of the cause of any fire alarm) when

any fire safety standard adopted under section 54-52 or 54-54 of this code requires emergency forces notification and/or a supervised sprinkler system for said premises.

(c) Only a licensed alarm contractor shall work on a fire alarm system. Effective July 1, 2015, each licensed alarm contractor shall have at least one individual on each job site currently certified by NICET (National Institute for Certification and Engineering Technologies) in fire alarm systems or equivalent as accepted by Georgia Automatic Fire Alarm Association (AFAA), Georgia Electronic Life Safety and Systems Association, and the county fire marshal. Proof of certification shall be kept on the person of the certified individual.

(d) All work performed on a fire alarm system shall require plans to be submitted to and approved by the fire marshal's office prior to any work being performed.

Effective July 1, 2016, all fire alarm plan submittals shall be made only by persons currently certified by NICET (National Institute for Certification and Engineering Technologies) in fire alarm systems or their equivalent as accepted by Georgia Automatic Fire Alarm Association (AFAA), Georgia Electronic Life Safety and Systems Association, and the county fire marshal. Proof of current certification shall be stamped on the plans and/or a copy of the certification shall accompany the submittal.

(e) Effective July 1, 2016, all documentation submitted to the fire marshal's office shall be completed and signed by persons currently certified by NICET

(National Institute for Certification and Engineering Technologies) in fire alarm systems or their equivalent as accepted by Georgia Automatic Fire Alarm Association (AFAA), Georgia Electronic Life Safety and Systems Association, and the county fire marshal. Such

documentation shall include, but not be limited to, record of completion forms, inspection testing and maintenance forms, permit applications, etc. Proof of current certification shall accompany the submitted documentation.

(f) Effective July 1, 2016, all inspection, testing, and maintenance of any alarm system shall be only by persons currently certified by NICET (National Institute for Certification and Engineering Technologies) in fire alarm systems or their equivalent as accepted by Georgia Automatic Fire Alarm Association (AFAA), Georgia Electronic Life Safety and Systems Association, and the county fire marshal.

(g) Electronic Security Association (ESA) National Training School (NTS) Certified Fire Alarm Technician (CFAT) Level II shall be an approved equivalent for NICET certification.

(h) All fire alarm systems shall be inspected annually in accordance with the currently adopted edition of NFPA 72. Maintenance records shall be submitted

to the Fire Marshal's Office. Submittal of records shall carry a fee as approved by the Cobb County Board of Commissioners. A tag shall be affixed to the fire alarm control panel indicating the date of inspection, the company responsible for the inspection, and the status of the fire alarm system using the following

color code: green shall indicate no deficiencies are present; yellow shall indicate deficiencies were found, but the fire alarm system will still function; and red shall indicate that the fire alarm system will not operate at all. All maintenance shall be performed by a licensed fire alarm company.

(Amd. of 2-26-08 (eff. 1-1-09); Amd. of 2-24-15; Amd.

of 2-23-16; Amd. of 5-23-17; Amd. of 11-20-25)

Reuniones que se refieren a esta sección

Encontradas: 1. Son reuniones de este gobierno cuyas actas o transcripciones automáticas nombran esta sección, o una ordenanza de su línea de historia, de la más reciente a la más antigua. Halladas por regla a partir de las propias palabras de esos registros. Una referencia es un enlace a otro registro, no una afirmación de que la sección se aplica o se cambió.

Leer este código donde se publica (Municode) La fuente es el código del condado tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.

Versión local-code:cobb-county/code/54-101@2025-11-20-bee70001de

El asistente puede decir lo que dice esta sección en esta edición, citándola y enlazándola. No aplicará la ley a su situación, y nada de esto es asesoría legal.