Sec. 70-57. Grease traps.
Sobre este texto
- As published by Municode, current through 2025-02-04
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
(a) Required. Grease traps shall be required for commercial or industrial establishments with onsite sewage management systems where it is determined by the county board of health that
grease may be introduced into the system in quantities that may adversely affect the operation of the system.
(b) Design. Plans and specifications for grease traps shall be submitted to the county board of health for approval. Grease traps shall be designed to provide a liquid capacity of not less than 125 gallons. Effluent from grease traps shall be
disposed of in a septic tank and not directly discharged to the absorption field.
(c) Construction. Grease traps shall be located, installed and constructed so that the temperature of the sewage will be reduced to permit congealing or separation of grease, and easy access for cleaning is provided.
(Co. Bd. Health Rule 290-5-26.12)