Part II - CODE OF ORDINANCES / Chapter 78 - UTILITIES / Article VI - BACKFLOW PREVENTION BY CONTAINMENT

Sec. 78-99. Fire protection systems.

Sobre este texto

  • As published by Municode, current through 2026-05-19
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

(1) For purposes of backflow-prevention by containment, if the service-connection to a premises; from the Coweta County Water Department potable water supply/system, is intended to be used for fire protection service it shall be classified and/or defined as follows:

(a) Dedicated service-connection. One that is designated to supply potable water for fire protection service only.

(b) Combination service-connection. One that is designated to supply potable water for both domestic use and fire protection service.

(2) To further associate the sources of water that may be used for fire protection and classes of fire protection systems, the following Georgia State Fire Code Classes shall also apply for backflow-prevention by containment.

CLASS 1: Directly supplied from Public water mains only; no pumps, tanks, or reservoirs;

no physical connection from other water supplies; no antifreeze or additives of any kind; all sprinkler drains discharging to atmosphere, dry wells or other safe outlets.

CLASS 2: Directly supplied from public water mains, same as Class L, except that authorization has been obtained for a booster pump to be installed in the supply line.

NOTE: Must have special approval and be permitted by the Coweta County Water Department. (See subsection 78-95(3).)

CLASS 3: Directly supplied from public water mains, same as Class L, PLUS one or more of the following: Elevated storage tanks or pressure tanks; fire pumps taking suction from above-ground covered reservoirs or tanks. All storage facilities shall be filled from the potable water supply and maintained in a potable condition.

CLASS 4: Directly supplied from public water mains, similar to Classes 1 and 2, and with an auxiliary water supply on or available to the premises; or an auxiliary water supply located within approximately 1,700 feet of the pumper connection.

CLASS 5: Directly supplied from public water mains, and interconnected with auxiliary supplies, such as: pumps taking suction from reservoirs exposed to contamination, or rivers and ponds; driven wells; mills or other industrial water systems; or where antifreeze or additives are used.

CLASS 6: Directly supplied from public water mains only, with or without gravity storage or pump suction tanks, and/or interconnections with industrial systems.

(3) The following terminology and definitions for types of fire protection systems shall also be applicable:

(a) Sprinkler system. Includes express riser pipes that convey water to the laterals that supply sprinkler heads.

(b) Standpipe system. Includes bulk riser pipes equipped with hose connections, usually at each floor and roof, for exclusive use by the fire department; plus laterals on each floor of certain facilities that supply water to hose cabinets for use by the occupants to control incipient fires until the fire department arrives.

(c) Combined system. Includes bulk and express riser pipes that supply both sprinkler and standpipe systems.

(4) Fire systems shall be further classified and defined as:

(a) Nonhazardous: Containing impurities Class 3 and lower. (Also see, Terminology for Pollutant - Appendix A)

(b) Hazardous: Containing impurities Class 4 and higher. (Also see, Terminology for Contaminant - Appendix A)

(5) Fire protection systems as defined by the Georgia State Fire Code shall be contained from the Coweta County Water Department water supply/system by backflow-prevention devices as indicated and that have approvals as required under section 78-97 of this article and classified or listed by the Underwriters Laboratories and Factory Mutual Insurance, as follows:

Class 1, 2 and 3 sprinkler systems, and nonhazardous standpipe or combined systems: Shall be contained by the installation of a double detector check backflow preventer.

Class 4, 5 and 6 sprinkler systems, and hazardous standpipe or combined systems: Shall be contained by the installation of a reduced pressure zone detector check backflow preventer.

Class systems with combination hazards: Shall be contained from the public water mains by procedures applicable to the component that requires the higher degree of protection.

(6) The purpose of certain checking devices used, or likely to be used, with fire protection systems is outlined below to call attention to those that are approved for use as backflowprevention devices and those that are not.

(a) Directional check: To provide directional flow only. Not an approved backflowprevention device.

(b) Alarm check: To signal an alarm; to summon the fire department, etc., when a sprinkler head flows water; and, on wet-pipe systems, to provide directional flow. Not an approved backflow-prevention device.

(c) Single detector check: To detect unauthorized use of water for other than fire service;

to detect leaks in fire protection systems; and, with by-pass check, to provide directional flow. Not an approved backflow preventer.

(d) Double check valve (DCV): To prevent backflow of polluted water into a potable water supply/system; and to provide directional flow. Approved for use with full service master or FM meters on a combination service connection only.

(e) Double detector check (DDC): To prevent backflow of polluted water from a fire protection system into a potable water supply/system; to detect unauthorized use of water; to detect leaks in the fire protection system; and, to provide directional flow.

Approved for use on a dedicated service connection.

(f) Reduced pressure zone check (RPZ): To prevent backflow of contaminated water into a potable water supply/system; and to provide directional flow. Approved for use on a combination service as in item (d).

(g) Reduced pressure detector check (RPDC): To prevent backflow of contaminated water from a fire protection system into a potable water supply/system; to detect unauthorized use of water; to detect leaks in the fire protection system; and to provide directional flow. Approved for use on a dedicated service as in item (e).

(7) Single detector checks that are used on nonhazardous fire protection systems Class 1, 2 or 3 may not be considered as a component part of a DDC backflow preventer. Specifically, the addition of a second single check to one of these devices may not be substituted for a double detector check (DDC) assembly, that is approved for backflow-prevention.

(8) It is intended that the approved double detector check (DDC) backflow preventer be in lieu of; not in addition to, the two checking devices already required in the supply to Class 1 and 2; or the double check valve BFP already required on Class 3 nonhazardous systems, and that the approved reduced pressure detector check (RPDC) be in lieu of the RPZ already required on hazardous systems. The only additional checking device intended is a 3 /4-inch

double check valve (DCV) or, reduced pressure zone (RPZ) in the 3 /4-inch copper bypass line, in conjunction with the bronze detector meter.

(9) The two shut-off valves required for periodic testing of the backflow-prevention device shall be OS and Y, FDA-approved fused epoxy coated inside and out, with resilient seats and the inlet valve shall include an approved test cock on the upstream side. All components shall be listed for fire protection service by Factory Mutual and Underwriters Laboratories.