Douglas County · Código de ordenanzas

Chapter 10 - FIRE PROTECTION

Sec. 10-17. Accessibility of buildings for firefighting equipment.

Sobre este texto

  • As published by Municode, current through 2026-03-31
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

(a) Reasonable accessibility shall be provided to and around all buildings for firefighting equipment, including ladder trucks on multiple-story projects. Accessibility shall be approved by the

fire chief or his designee.

(b) Accessibility for firefighter's equipment shall be maintained throughout all stages of construction.

(c) Minimum widths of access roads, excluding parking, shall be twenty (20) feet. Minimum turning radius shall be thirty-two (32) feet. All access roads and fire lanes shall be capable of supporting

the loads of fire apparatus and shall have a minimum of thirteen (13) feet, six (6) inches of vertical clearance.

(d) All access roads in excess of one hundred fifty (150) feet in length shall be provided with an approved area for turning around fire apparatus.

(e) Gates securing fire apparatus access shall be provided with an automatic gate-opening device if the gates are controlled by electronic means.

An approved siren operated sensor shall activate the gate-opening device.

(f) Gates securing fire apparatus access shall be a minimum fourteen (14) feet in clear width for divided lanes and twenty (20) feet for a single lane. Gate shall be swing or sliding type. Fire access lanes shall be straight and have no turns for fifty (50) feet on both sides of security gate.

(g) Additional fire apparatus access may be required based on the fire chief or his designee's opinion.

Historia

La línea de historia que la fuente imprime al final de la sección.

(Ord. of 8-18-09)

Leer este código donde se publica (Municode) La fuente es el código del condado tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.

Versión local-code:douglas-county/code/10-17@2026-03-31-f3a9a2d8b2

El asistente puede decir lo que dice esta sección en esta edición, citándola y enlazándola. No aplicará la ley a su situación, y nada de esto es asesoría legal.

Douglas County Code of Ordinances, Sec. 10-17. Accessibility of buildings for firefighting equipment | Georgia Commons