Chapter 10 - FIRE PROTECTION

Sec. 10-18. Fire hydrant installation—Prior to construction.

Sobre este texto

  • As published by Municode, current through 2026-03-31
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

(a) Water mains and fire hydrants, when required by the county, shall be installed, or shall be under water pressure and ready for firefighting

before any sheeting may be installed on walls and roofs of buildings other than fire-resistant construction.

(b) All fire hydrants, fittings, valves and fire department connections shall be approved by the Douglasville-Douglas County Water and Sewer Authority and the fire chief or his designee. Fire department connections shall not be less than eighteen (18) inches or more than forty-eight

(48) inches above the level of the adjoining ground or paving. The thread of such connections shall be uniform with that used by the fire department. The fire department connection shall

be two and one-half (2) inches in diameter and one (1) four and one-half (4) inches in diameter . Fire hydrants shall be painted silver in color.

(c) Fire hydrants shall be installed in accordance with the current state adopted edition with amendments for NFPA 24 as modified, Standard for the Installation of Private Fire

Service Mains and Their Appurtenances, and shall have not less than six-inch connections with the mains. The number, size and arrangement of the outlets, the size of the main valve opening and the size of the barrel shall be

suitable for protection to be provided and shall be approved by the Douglasville-Douglas County Water and Sewer Authority and the fire Chief or his designee. Fire hydrants shall be placed no closer than fifty (50) feet from the nearest building to be protected. Where it is impossible to place them at this distance, they may be put

closer to the building provided they are set in locations where the chance of injury by falling walls is minimal and where firefighters are not likely to be driven by smoke or heat and must be approved by the fire chief or his designee.

(d) The size and shape of the operation nut, as well as the direction the hydrant stem operates, shall be uniform with hydrants in the county water distribution system's specifications.

(e) A three-way fire hydrant shall be located within fifty (50) feet of a fire department connection or standpipe connection. Fire hydrant shall be on the same side of the street as the fire

department connection or standpipe connection.

Historia

La línea de historia que la fuente imprime al final de la sección.

(Ord. of 8-18-09)