Hall County · Código de ordenanzas
Part III - ETHICS BOARD / Title 13 - PUBLIC SERVICES* / Chapter 13.10 - SEWERS AND SEWAGE DISPOSAL / Article I - PUBLIC SEWERS
13.10.1350. Fat, oil, grease, and sand interceptors required and maintained.
Sobre este texto
- As published by Municode, current through 2026-05-28
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
A. No food processing industry, commercial facility, maintenance or service facility such as a service station, auto repair shop, car wash, metal working establishment, etc., shall discharge into the sanitary sewer system without a wastewater discharge permit issued by the county. Application for such permit must be made on a form furnished by the county. The permit is valid for up
to five years and is nontransferable.
B. F.O.G./sand separator required. All new maintenance and service facilities, restaurants, institutional kitchens, or other food service establishments defined as commercial users of the system, shall provide approved F.O.G. and settleable solids removal equipment or facilities sufficient to meet the limitations set forth in this article. The number and size(s) of the system(s)
shall be determined by the county. Existing commercial users will be assessed on an individual basis, and will require approval by the county.
(1) The separator(s) shall exclude sanitary wastewater and be located outside of any building and accessible for proper maintenance and inspection.
(2) The separator(s) must be located in an area that will allow for the dumpster pad to be connected.
(3) In areas where additional weight loads may exist, the separator(s) shall be installed with traffic bearing covers.
(4) The separator must be a minimum of 1,500 gallons and have three baffles, and three inspection openings provided, one over the influent pipe, another over the center baffle, and another over the discharge pipe for inspection purposes.
(5) The equipment or facilities shall be installed and maintained by the originator.
(6) All food service industries defined as commercial facilities shall be required to have a separate water meter and back-flow
device, unless a specific variance is granted by the director.
(7) Alternative treatment methods. The use of any alternative method of treatment is prohibited without written approval by the county. Alternative treatment systems, such as mechanical grease recovery devices, shall only be used only after
evaluation and authorization by the county.
(8) The use of chemicals, enzymes and bacteria is prohibited, unless specifically authorized in writing by the county, and only after site specific monitoring and data
collection has been performed. The use of any additives shall not be considered as an alternative to an adequate treatment system or in lieu of regular maintenance, as prescribed in this article.
(9) All F.O.G. or sand separators shall be maintained at the originator's expense.
Maintenance shall include the complete removal of all contents of the separator.
The county has established the following minimum pumping schedule and may increase or decrease the pumping frequency based on the originator's compliance with
this article:
Class Description of User F.O.G. or Sand Separator Pumping Frequency* I Food establishments with an under-the-counter grease trap. Monthly II Food establishments with an in ground grease trap of at
least 1,500 gallons and serving less than 100 customers in a 24-hour day.
Two times per year III Food establishments with an in ground grease trap of at least 1,500 gallons and serving 100 customers to 250 customers in a 24-hour day.
Four times per year IV Food establishments with an in ground grease trap of at least 1,500 gallons and serving more than 250 customers in a 24-hour day.
Monthly V Wash bay grit removal sand trap(s) Monthly VI Self-serve carwash with less than four wash bays Four times per year VII Automatic carwash owned/operated by a service station Four times per year VIII Self-serve carwash with more than four wash bays Monthly
IX Combination self-serve and automatic carwash Monthly X Full service automatic carwash Monthly
* The director may in writing or verbally increase or decrease a user's grease trap pumping frequency on a case-by-case basis based on actual observation of material buildup in the grease trap.
C. Pumping requires the complete removal of the entire contents of the trap with no reintroduction of any portion of the waste into the trap. The county may seek additional enforcement action
under O.C.G.A. § 12-8-2.
D. A grease trap waste hauler must obtain a grease trap waste disposal manifest prior to removal or transporting waste for disposal. It is the grease trap owner's responsibility to ensure the
hauler possesses said manifest prior to pumping.
Otherwise, the owner is in noncompliance with this article and shall be subject to all applicable fines and penalties included herein.
E. Owners to maintain pretreatment and flowequalizing facilities. Where preliminary treatment or flow-equalizing facilities are provided for any waters or wastes, they shall be maintained
continuously in satisfactory and effective operation by the owner at his expense.
Historia
(Res. of 1-8-09(1), §§ 1, 2(Exh. A))
Leer este código donde se publica (Municode) La fuente es el código del condado tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.