Part II - CODE OF ORDINANCES / Chapter 14 - ENVIRONMENT / Article III - FLOOD PREVENTION AND CONTROL / Division 4 - STANDARDS, SPECIFICATIONS AND REGULATIONS

Sec. 14-271. Elevated buildings.

Sobre este texto

  • As published by Municode, current through 2019-01-10
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

Elevated buildings in special flood hazard areas, shall comply with the following requirements:

(1) All new construction or substantial improvements of existing structures that include any fully enclosed area located below the lowest floor formed by a foundation and other exterior walls shall be designed so as to be an unfinished or flood-resistant enclosure.

(2) The enclosure shall be designed to equalize hydrostatic flood forces on exterior walls by allowing for the automatic entry and exit of floodwater.

(3) Designs for complying with this requirement must either be certified by a professional engineer or architect or meet the following minimum criteria:

a. Provide a minimum of two openings having a total net area of not less than one square inch for every square foot of enclosed area subject to flooding;

b. The bottom of all openings shall be no higher than one foot above grade; and

c. Openings may be equipped with screens, louvers, valves or other coverings or devices provided they permit the automatic flow of floodwater in both directions.

(4) So as not to violate the lowest floor criteria of this article, the unfinished or floodresistant enclosure shall be used only for parking of vehicles, limited storage of maintenance equipment used in connection with the premises, or entry to the elevated area, and the interior portion of such enclosed area shall not be partitioned or finished into separate rooms. The interior portion of such enclosed area shall not be partitioned or finished into separate rooms.

Historia

La línea de historia que la fuente imprime al final de la sección.

(Ord. of 7-19-2010, art. 4, § A)