Sec. 10-55. Electrical code.
Sobre este texto
- As published by Municode, current through 2023-04-18
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
The National Electrical Code is adopted, with the following amendments:
(1) Disconnects are not required in residential dwellings where the electrical panel is within 15 horizontal feet of the meter disconnects are required otherwise as per code);
(2) All bond wires shall be crimped in boxes;
(3) Any circuit with a capacity of 40 amperes or less is required to be copper wire only (no aluminum or copper clad aluminum wire allowed);
(4) Each of the following appliances must be placed on an individual circuit with a minimum #12 size wire: refrigerators, freezers, well pumps, attic fans, garbage disposals, window air conditioners, microwave ovens, etc.;
(5) A minimum of #14 size wire must be used in bedrooms, hallways, living rooms, dens, bathrooms and outside acres, including carports;
(6) A minimum of #12 size wire must be used in utility rooms, laundry rooms, dining rooms, kitchens and breakfast areas;
(7) Ground fault interrupter (GFI) protection shall be required as follows:
a. Kitchen circuits. One GFI protection device required. (NOTE: Not more than two outlets are allowed per circuit in kitchens)
b. Bathrooms. One GFI protection device required for each level of multi-story dwellings.
(NOTE: GFI protection shall be sufficient for up to five outlets on a single circuit);
c. Outside receptacles (including garages and carports). One GFI protection device required.
(NOTE: GFI protection shall be sufficient for up to five outlets on a single circuit);
(8) No more than two outlets may be placed on any circuit serving the kitchen area;
(9) A minimum of #10 size wire with ground must be used on any circuit serving a water heater; a minimum of #10-3 size wire must be used on any circuit serving a clothes dryer, surface unit or oven;
(10) The following is the minimum size for any residential service:
a. Dwelling size less than 1,000 square feet: minimum 100 amp main service.
b. Dwelling size 1,000 to 2,000 square feet: minimum 150 amp main service.
c. Dwelling size over 2,000 square feet: minimum 200 amp main service.
d. Total electric dwellings (except multifamily units of less than 1,000 square feet in size) must have a minimum of 200 amp main service.
(11) Temporary services (saw services) may be allowed for up to 12 months. If additional time is needed, applicants may apply for continuance of service. Substantial progress must be demonstrated at this time.
Historia
(Code 2001, § 36-110; Ord. of 9-4-1990)