Part - CODE OF ORDINANCES / Chapter 66 - UTILITIES / Article II - WATER / Division 5 - WATER AND WASTEWATER SYSTEMS

Sec. 66-261. Backflow prevention.

Sobre este texto

  • As published by Municode, current through 2026-04-07
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

(a) When required. All wastewater treatment plants, commercial businesses, industries or institutions that handle toxic or hazardous chemicals shall be required to install backflow prevention mechanisms. Additionally, approved backflow preventers or vacuum breakers shall be installed with all plumbing fixtures or equipment for which the potable water supply outlet may be submerged without the protection of a minimum air gap. The particular backflow prevention devices utilized in any given situation shall be as specified in the plumbing code or as approved by the department director.

(b) Minimum required air gap. The minimum required air gap shall be measured vertically from the lowest end of a potable water outlet to the flood rim or line of the fixture or receptacle into which it discharges. The minimum required air gap shall be twice the effective opening of a potable water outlet unless the outlet is a distance less than three times the effective opening away from a wall or similar vertical surface, in which case the minimum required air gap shall be three times the effective opening of the outlet. In no case shall the minimum required air gap be less than is provided in the plumbing code.

Historia

La línea de historia que la fuente imprime al final de la sección.

(Ord. of 2-4-2003, § 2-81)