Chapter 33 - DATA CENTERS
Sec. 33-8. Fire safety and security standards for data centers.
Sobre este texto
- As published by Municode, current through 2026-06-02
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
(a) Data centers are required to install active clean-agent fire suppression systems with high sensitivity smoke detectors.
(b) Data centers are required to provide an exterior emergency electrical termination switch, clearly designed for public safety access.
(c) Data centers are required to install an eight-foot security fence around the perimeter of the primary data center structure.
(d) Data centers are required to install a Knox Box on the property and display 24-hour emergency contact signage at the entrance of the primary structure.
Historia
(Res. No. 2026-180, § 1, 3-3-2026)