(a) Ownership. All fire hydrants installed within the unincorporated area of Putnam County shall be owned by and under the direct supervision of the respective owners. Owners shall be required to provide the Putnam County Fire Chief with a complete listing of the number and location of all fire hydrants under their supervision.
(b) Fire hydrants required. All public well or water supply systems, as defined in this Code, shall provide fire hydrants as a primary means of fire suppression. This requirement shall apply to newly constructed systems and any expansion of existing systems where such expansion would add service for 15 or more connections or add service for 25 or more persons on a daily basis whether such expansion is completed at one time or in several phases.
Owners or operators of existing public well or water supply systems are hereby prohibited from removing fire hydrants currently installed in said systems except as provided below.
Existing public well or water supply systems which do not include fire hydrants shall not be required to install fire hydrants unless the system is expanded as provided above.
(c) Fire hydrant standards. All fire hydrants incorporated into a public well or water supply system shall be installed and maintained by the respective owners in accordance with the most recent version of the International Fire Code including any appendices as adopted by Putnam County. Said standards include, but are not limited to, minimal distance between fire hydrants, location with respect to public right-of-way, design and construction specifications, and pressure/flow capacity. All fire hydrants shall be fitted with a Storz nozzle, a non-threaded outlet connector able to allow a quarter-turn connection, or comparable connector, as approved by the Putnam County Fire Chief. Such fire hydrants shall be serviced by water mains no less than eight inches in diameter.
(d) Fire chief granted authority. The Putnam County Fire Chief, or his/her designee, is hereby granted the authority to inspect, test and approve all fire hydrants situated within the unincorporated area of Putnam County. The Putnam County Fire Chief shall keep all records of the location and test results of all fire hydrants under this authority. The fire chief, or his/her designee, shall indicate the result of testing by color-coding the fire hydrant according to the International Fire Code standards. Newly installed fire hydrants shall be tested within 180 days of installation. Existing fire hydrants shall be tested at intervals of no less than two years. No owner of a fire hydrant included under this authority shall interfere with or restrict the ability of the Putnam County Fire Chief to exercise this authority.
(e) Fire hydrant out-of-service. The owner of any fire hydrant under their supervision which is known to be inoperative or out of service for any reason shall promptly report the same to the Putnam County Fire Chief. Any fire hydrant found, on testing, to fail to meet the standards set forth above shall be designated as out-of-service. The Putnam County Fire Chief shall notify the owner, in writing, of any fire hydrant designated as being out-of-service within ten days of such designation. The notification may be by personal service or U.S.
Postal Service, registered letter.
(f) Owner duty to repair. Upon notification of a fire hydrant being out-of-service, it shall be the duty of the owner to repair or replace the defective fire hydrant so as to place it back in service within 90 days of receiving notification. Alternatively, at the option of the owner, the defective fire hydrant may be physically removed from the system, providing however that the distance between the remaining, approved fire hydrants be no less than 1,000 feet.
(g) Violations. Notwithstanding any other provisions of this Code, any violation of this code section shall be punishable by a minimum fine of $50.00. Each day the violation continues shall constitute a separate offense.
Historia
(Ord. of 12-18-2007; Ord. of 3-18-2008; Ord. of 1-19-2016; Ord. of 7-19-2022(1))
Reuniones que se refieren a esta sección
- Putnam County Board of Commissioners, 5 de abril de 2024 (Actas)Se refiere a esta sección en las actas: “Section 32-19”, “Section 32-19”
Leer este código donde se publica (Municode) La fuente es el código del condado tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.