in new and existing buildings
(IFC 510).
(a) Approved in-building, two-way emergency responder communication coverage for emergency responders shall be provided in all new and existing buildings. In-building, two-way emergency responder communication coverage within the building shall be based on the existing coverage levels of the public safety communication systems utilized by the jurisdiction.
Exceptions:
(1) Where approved by the fire code official, a wired communication system in
accordance with Section 907.2.13.2 shall be permitted to be installed or maintained instead of an approved radio coverage, or otherwise-required communication-coverage, system.
(2) Where it is determined by the official fire code that the communication coverage
system is not needed. In order to make this determination, the fire code official may require an approved type of evaluation and/or modeling of communication coverage signal strength be conducted, at the expense of the building owner, for
new and existing buildings, new portions of buildings, or buildings or portions
thereof otherwise triggering the provisions of this Code.
(3) In facilities where emergency responder communication coverage is required and
such systems, components or equipment required could have a negative impact on the normal operations of that facility, the fire code official shall have the authority to accept an automatically activated
emergency responder communication coverage system.
(4) One- and two-family dwellings and townhouses.
(b) The building shall be considered to have acceptable in-building, two-way emergency responder communication system coverage where signal strength measurements in 95 percent of all areas on each floor of the building, and 99 percent of each critical area as designated below, meet the signal strength requirements. Critical areas shall include the following:
(1) At all fire alarm control panels.
(2) At fire fighter's smoke control panels.
(3) At the main electrical panel(s).
(4) Throughout emergency and standby power rooms.
(5) Throughout a fire command center complying with Section 508.
(6) Throughout exit stairs.
(7) Throughout areas of refuge.
(8) Throughout fire pump rooms.
(9) Throughout elevator machine rooms and elevator lobbies.
(10) Throughout building lobbies.
(11) Locations as determined by the fire code official.
(c) Maintenance. All systems and components shall be tested annually in accordance with IFC
510.6. A system test and inspection report shall be maintained on site for inspection by the fire marshal's office. A tag shall be placed on the head end cabinet indicating the date of the last test and the results of the test. All test reports shall be submitted to the FMO in an expeditious manner. Any system that fails annual testing should be reported to the FMO within 48 hours of testing. Should a system fail to provide adequate signal, cause interference, or fail to perform as originally installed, the fire marshal is authorized to order the testing of the system and repair to original installation standards or the current adopted edition of the standard. The fire marshal is authorized to order that cellular signal boosting systems that interfere with the public safety radio system be tested or disconnected pending testing in order to eliminate interference.
Historia
(Ord. No. O-2025-16, § 6, 7-8-2025)
Leer este código donde se publica (Municode) La fuente es el código del condado tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.