Sec. 50-82. Grease traps.
Sobre este texto
- As published by Municode, current through 2026-01-27
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
(a) Grease traps required. Grease traps shall be required for commercial or industrial establishments with on-site sewage management systems where it is determined by the county board of
health that the amount of grease introduced into the system is in excess of 50 mg/I.
(b) Grease trap design. Plans and specifications for grease traps shall be submitted to the county board of health for approval. The county
board of health shall review the grease trap design in accordance with minimum design and construction criteria established by the department's current Manual for On-Site Sewage Management Systems. Effluent from grease traps shall be disposed of in a septic tank and not directly discharged to the absorption field. Grease traps shall be located, installed and constructed so that the temperature of the sewage will be reduced to permit congealing or separation of grease, and easy access for cleaning is provided.
Historia
(Ord. No. 0-2002-01, § 1(9-6012), 1-8-2002)