Sec. 98-44. Cooling tower water efficiency.
Sobre este texto
- As published by Municode, current through 2026-01-27
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
(a) Once-through cooling. Once-through cooling using potable water is prohibited.
(b) Cooling towers and evaporative coolers.
Cooling towers and evaporative coolers shall be equipped with makeup water and blow-down meters, conductivity controllers and overflow alarms. Cooling towers shall be equipped with efficiency drift eliminators that achieve drift reduction to 0.002 percent of the circulated water volume for counterflow towers and 0.005 percent for crossflow towers.
(c) Cooling tower makeup water. Water used for air conditioning, and cooling towers shall not be discharged where the hardness of the basin water is less than 1,500 mg/L. Exception: Where any of the following conditions of the basin water are present: total suspended solids exceed 25 ppm, CaC03 exceeds 600 ppm, chlorides exceed 250 ppm, sulfates exceed 250 ppm, or silica exceeds 150 ppm.