Sec. 98-68. Spacing of fire hydrants.

Sobre este texto

  • As published by Municode, current through 2026-01-27
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

(a) Public fire hydrant spacing.

(1) All water mains in the county shall have fire hydrants installed at least every 500 feet. Hydrant distance shall be measured along the centerline of the street or

roadway.

(2) In all nonresidential or mixed-use areas, in order to meet minimum required

hydrant water flow, additional hydrants shall be installed where designated by the fire chief or authorized designee.

(b) Private fire hydrant spacing. Private fire hydrants shall be located so that all parts of a building are within 500 feet of one or more fire hydrants.

(c) Variance. Any variance for fire hydrant spacing must be approved by the fire chief or authorized designee. Such variances must be noted on appropriate site drawings.

Historia

La línea de historia que la fuente imprime al final de la sección.

(Ord. No. 2007-07, § 1, 3-27-2007)