Sec. 28-417. Secondary metering.

Sobre este texto

  • As published by Municode, current through 2026-07-09
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

Whenever a property upon which a sewer user charge is imposed under this article uses water for an industrial or commercial purpose, which water so used is not discharged into the sewerage system of the Authority, the quantity of water so used and not discharged into the Authority's sewers shall be excluded in determining the sewer user charge of the owner or occupant; provided that the quantity of water so used and not discharged into the Authority sewers is measured by a device or meter (called a secondary meter) approved by the Authority and installed by the owner or occupant without cost to the Authority. The sewer user charge based upon the consumption of water to be paid by the owner or occupant of such property shall be computed at the rates provided in this article less the quantity not discharged into the Authority's sewers. The Authority reserves the right to require calibration of secondary meters when appropriate. A secondary meter shall meet the following requirements:

(1) Meters should read in 100 cubic feet.

(2) Meters must be located either in an outdoor meter box or vault, or inside the user's building or structure in a clean, dry, safe place not subject to wide temperature variations so that the meter can be easily examined, read, or removed.

(3) The user shall, at its expense, provide suitable pipe connections and shut-off valves, 1 each at the inlet and outlet sides of the meter.

(4) The meter box or vault must be constructed to protect the meter from freezing and damage by vehicular traffic, and its location and design shall prevent, as far as possible, the inflow of surface water.

(5) Any changes in location of secondary meters, malfunctions, replacements, or any other changes in the approved secondary meter installation must be reported to the Authority in writing. Also, a copy must be forwarded to the water company containing all pertinent information regarding that particular meter.

(6) No retroactive credits will be issued if the holder of the secondary meter permit fails to comply with the rules and regulations in force at any particular time.

(7) If any water exempted from the sewer service charge is returned to the sewer system at any time or point, a metering device shall be installed. Any flow registered through such a meter shall be charged for sewer service.

(8) Any secondary meter must be easily accessible by the Authority. If this is not possible, remote read meters shall be installed and protected from any magnetic interference. It is the responsibility of the permit holder to assure the accuracy of the remote read to the installed meter.

(9) All meters must be calibrated and certified for accuracy once every 18 months. The certification of the inspection or a copy thereof has to be forwarded to the Authority.

Historia

La línea de historia que la fuente imprime al final de la sección.

(Ord. No. O-03-22, Exh. A, 11-10-2022)