Sec. 16-303. Facilities plans.

Sobre este texto

  • As published by Municode, retrieved 2026-11-11
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

All detention and or retention facilities plans shall be at a scale of not less than one-inch equals 50 feet with a maximum contour interval of two feet. The plans shall be based on a stage-storage design and shall meet the following requirements:

(1) Maximum storage requirements for the proposed facility shall be based on the storage volume required for the 50-year frequency storm event, and the 100-year storm event must be routed through the facility without overtopping the embankment, by use of an emergency spillway or other structure.

(2) The stage-storage design increment shall not exceed one-foot in elevation.

(3) The outlet device shall be designed to limit post-developed runoff rates to less than or equal to the pre-developed rates for the two-, five-, ten-, 25-, and 50-year frequency storms.

(4) The type and size of pipes to be used for the outlet along with detail drawings and specifications for all facilities shall be shown.

(5) Actual results obtained from routing the two-, five-, ten-, 25-, 50-, and 100-year post-developed storm hydrographs through the facility shall be included.

(6) A summary chart showing maximum facility elevations, maximum water surface elevations, storage required, and pre-developed and post-developed discharge rates for the two-, five-, ten-, 25-, 50- and 100-year frequency storms shall be included.

(7) Stormwater detention/retention facilities shall be graded so as to provide positive drainage. The minimum slope along the bottom of the facility shall be two percent.

Side slopes shall not be steeper than three feet horizontal to one-foot vertical.

Historia

La línea de historia que la fuente imprime al final de la sección.

(Ord. No. 2007-1, 4-9-2007; Ord. No. 2021-14, 2-14-2022)

Leer este código donde se publica (Municode) La fuente es el código de la ciudad tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.

Versión local-code:byron/code/16-303@2026-11-11-20405724ba

El asistente puede decir lo que dice esta sección en esta edición, citándola y enlazándola. No aplicará la ley a su situación, y nada de esto es asesoría legal.

Byron Code of Ordinances, Sec. 16-303. Facilities plans | Georgia Commons