A. General.
1) All materials used in the work including equipment shall be new and unused materials of a reputable U.S. manufacturer conforming to the applicable requirements of these specifications, and no materials shall be used in the work until they have been approved by the city.
2) Any reference to a AWWA, ANSI, ASTM or other such specification shall mean the latest revision published.
3) Any pipe, solder or flux used in the installation or repair of the water lines shall be lead free. Pipes and fittings shall not contain more than 8.0 percent lead and solder and flux shall not contain more than 0.2 percent lead.
B. Water main.
1) Ductile iron pipe.
a. Ductile iron pipe shall be used for all water mains, except where the city engineer approves otherwise.
b. Ductile iron pipe shall be thickness class 50, designed in accordance with AWWA C150 and manufactured in accordance with AWWA C151.
c. Ductile iron pipe shall have an outside bitumastic coating per AWWA C151. It shall have an inside standard cement lining with bituminous seal coat per AWWA C104.
d. Pipe joints.
i. Except where restrained, flange, or mechanical joints are specified, straight pipe joints shall be push on, rubber gasket type such as Fastite as manufactured by American Ductile Iron Pipe or alternate acceptable to the city conforming to
AWWA C111.
ii. Pipe shall be in 18-foot to 20-foot nominal lengths with standard deflection pipe sockets.
iii. Where restrained joints are shown, the joints shall be "flex-ring" type as manufactured by American Ductile Iron Pipe, TR Flex as manufactured by U.S. Pipe or alternate acceptable to the city.
e. Where river crossing pipe is required, the pipe shall be "flex-lok boltless ball joint pipe" as manufactured by American Ductile Iron Pipe or alternate acceptable to the city.
f. Where specified, flanged pipe shall meet AWWA C151 specifications and be used with fittings meeting AWWA C110 or AWWA C153.
g. Certificates of conformance with the foregoing specifications shall be furnished with each lot of pipe supplied.
2) Copper tubing for water service laterals.
a. Service lateral pipe shall be copper service pipe, type K, soft temper, seamless copper tubing, conforming to ASTM B-88. Compression joints will be used.
b. Service line size shall be one inch for single residential service and one inch for double residential service. Service line size shall be one inch minimum for all other types of developments.
c. All service lines smaller than four inches in diameter shall be copper. Service lines four inches in diameter and larger shall be ductile iron.
3) PVC casing for services.
a. Long side service lines shall be bored and encased in PVC pipe.
b. PVC casing pipe used for long-side services shall be schedule 40 and a minimum of two inches in diameter for residential developments and four inches in diameter for all other type developments.
4) Casing pipe.
a. Casing pipe, where required under the street, shall be smooth steel pipe conforming to ASTM A-139, Grade B, electric fusion welded steel pipe.
b. The pipe shall have minimum yield strength of 35,000 psi.
c. The exterior and interior of the pipe shall have a bitumastic varnish coating.
d. Minimum wall thickness: 0.250 inch or as required by the DOT or other governing body having jurisdiction over the crossing.
5) Ductile iron pipe fittings.
a. Fittings shall be ductile iron and furnished in accordance with AWWA C110 or AWWA C153, and shall be a minimum of 350 psi pressure class rating.
b. Joints shall be mechanical joint with retainer glands conforming to AWWA C111, except where approved otherwise by the city.
c. Cement mortar lining conforming to AWWA C104 or fusion-bonded epoxy coating conforming to AWWA C116 shall be furnished for fittings.
C. Fire hydrants.
1) All fire hydrants shall comply in all respects with city standards and shall be designed and manufactured to comply with the requirements of AWWA C502.
2) The hydrants shall be designed for 250 pounds working pressure.
3) The hydrants shall be of simple design, easy to operate, effectively and positively drained and protected from damage by freezing, and convenient for repairing and replacing parts.
4) Hydrants shall be equipped with one four and one-half-inch diameter pumper nozzle and two two and one-half-inch diameter hose connections, which shall have threads meeting the latest requirements of the state fire insurance commission.
5) Hydrants shall have a safety flange on the barrel and a safety coupling on the valve stem to prevent damage to barrel and stem in case of traffic accident. Safety coupling shall be set two inches to six inches above the finish grade.
6) Hydrants shall be M&H Style 129 model or Mueller Company's Super Centurian traffic model.
7) The connection at the base of the hydrant shall be mechanical joint with ductile iron retainer gland for six-inch ductile iron pipe. The valve opening shall meet the requirement of the AWWA Specifications for a five and one-quarter-inch hydrant. The valve, valve seat and inner working parts shall be easily accessible. The height from the surface of the ground to the bottom of the hose nozzle shall be no less than 24 inches.
8) Each hydrant shall be neatly painted with Sherwin Williams Product No. C19387 Chrome Aluminum Spray Enamel paint.
9) Each hydrant shall be tested to 200 psi. The first test shall be made with the valve closed.
The second test shall be made with the main valve open but all nozzles closed. While the test is being carried on, the hydrant shall be subjected to a hammer test. Any hydrant showing defects by leakage, sweating, or otherwise shall be rejected. The barrel and all parts shall withstand these tests. These tests shall be made in the field after the hydrants are installed.
10) Leads from the main line to the fire hydrant shall use six-inch ductile iron pipe and shall have a six-inch gate valve between the main line and fire hydrant. The valve shall be connected to the main line by using a locking (anchoring) hydrant tee. Retainer glands or steel rods must be used to insure adequate connection of fire hydrant to valve. When the hydrant is close enough to the valve to allow its use, the hydrant shall be connected to the valve by using an anchor coupling acceptable to the city.
D. Valves and accessories.
1) Gate valves.
a. Valves 16 inches and smaller shall be gate valves.
b. The valves shall be of non-rising stem design, and have an iron body, bronze mounted, resilient seated, meeting all requirements of AWWA C509 or AWWA C515.
c. All interior ferrous surfaces of valves shall have a fusion-bonded epoxy coating meeting the requirements of AWWA C550.
d. Valves shall be designed for a minimum working pressure of 250 psi and shall have two-inch square operating nuts, except in meter vaults where handwheels shall be installed.
e. Valves for pipe smaller than four inches in diameter shall have handwheels suitable for use inside standard valve boxes.
f. Valves shall open when turned counter-clockwise.
g. Valves sized two inches through 12 inches shall be Mueller Co. A-2360 with mechanical joints or alternate acceptable to the city.
h. Fourteen-inch and 15-inch valves shall be Mueller Co. A-2361 with mechanical joints or alternate acceptable to the city.
i. Mechanical joints shall be fitted with retainer glands.
j. Where flange joints are used, flanges must meet the requirements of AWWA C115.
2) Butterfly valves.
a. Valves larger than 16 inches in diameter shall be butterfly valves.
b. All butterfly valves shall be bubble-tight closing at the rated pressure with flow in either direction, and shall be satisfactory for applications involving throttling service and frequent operations or operations after long periods of inactivity.
c. Valves shall meet the full requirements of AWWA C504, for 250 psi working pressure and shall be suitable for above ground or buried service.
d. All interior ferrous surfaces of valves shall have a fusion-bonded epoxy coating meeting the requirements of AWWA C550.
e. Valve bodies shall be equipped with integrally cast mechanical joint ends meeting AWWA C111. Mechanical joints shall be furnished with retainer glands.
f. Butterfly valves installed underground shall come equipped with a manual operator.
This manual operator shall be of the traveling nut, self-locking type and shall be designed to hold the valve in any intermediate position between fully open and fully closed without creeping or fluttering. Operators shall be equipped with mechanical stop-limiting devices to prevent over travel of the disc in the open and closed positions.
g. Valves shall open when turned counter-clockwise. Operators shall be fully enclosed and designed for buried operation.
3) Valve boxes.
a. Valves boxes for valves shall be approved standard cast iron adjustable shaft boxes having a minimum shaft diameter of five and one-quarter inches.
b. The casing shall be coated with two coats of bitumastic paint.
c. The lids of all boxes shall bear the word "water" or the letter "W".
4) Air and vacuum relief valve assemblies.
a. The valve shall be a combination air/vacuum- double orifice automatic air release valve with two-inch connection to the pipe line.
b. The valve shall be of one-piece body design.
c. The internal parts shall have a small orifice within tripod for small air discharge and a big orifice within bonnet of base housing for main air discharge and allow air to enter in the event of a vacuum condition.
d. The material of the body and the flow shall be Delrin (Poloximethylene, POM).
e. The valve sealing is rubber made of EPDM.
f. The valve shall have a protection cap of PE.
g. Air and vacuum valves shall be manufactured by H-TEC or alternate acceptable to the city.
h. Valves shall be a minimum of one inch.
i. Gate valves between water main and air release valve shall be bronze, solid wedge with screw connection equal to Jenkins Company Figure 325J or alternate acceptable to the city.
j. Meter box shall be equal to the NDS Style D-1200 or alternate acceptable to the city.
5) Tapping sleeves.
a. Tapping sleeves for existing water mains sized four inches through 12 inches shall be either an American Flow Control Series 2800, or a Ford Stainless Style FAST Tapping Sleeve or alternate acceptable to the city. Sleeves shall have a flanged connection to the tapping valve.
b. Tapping sleeves for existing water mains sized larger than 12 inches in diameter shall be an American Flow Control Series 1004 or alternate acceptable to the city. The sleeve shall be mechanical joint type with a flanged connection to the tapping valve. It shall be capable of withstanding a working pressure of 250 psi for the pipe size and type shown.
6) Tapping valves. Tapping valves shall be American Flow Control Series 2500, mechanical joint by flanged ends, 250 psi, or alternate acceptable to the city.
7) Pipe connection couplings.
a. Pipe connections between new pipe and existing pipe shall be made with Dresser Style 90 long steel couplings for pipe sizes two inches and below.
b. For pipe sizes above two inches, M.J. solid sleeves (long style) shall be used.
c. Spacer rings must be used at all solid sleeve locations. A spacer ring is defined as a short section of pipe cut to fit into the gap between the two plain ends of pipe at the sleeve location.
d. Field joints shall be made to insure permanently tight joints under all reasonable conditions of expansion, contraction, shifting, etc.
8) Curb stops.
a. All metal parts of curb stops shall be made of bronze.
b. The stops shall be Ford B43-332W with padlock wings or alternate acceptable to the city for copper service pipe.
c. The stop shall be operated with a combined cap and tee and shall open when turned counter-clock wise.
d. The stop shall be compression joint inlet with meter swivel nut outlet.
9) Service line couplings.
a. Service line pipe couplings shall be compression style Ford C44 or alternate acceptable to the city.
b. Branch connection shall be one inch by three-quarters inch by three-quarters inch Ford Y44-243 or alternate acceptable to the city.
c. A cut-off valve (such as a Ford B44-444 Curb Stop) shall be installed on the water main side (the one-inch side) of the wye and shall be buried without a valve box.
d. Female compression adapters shall be a Mueller-H-15451 or alternate acceptable to the city.
e. Male compression adapters shall be a Mueller-H-15428 or alternate acceptable to the city.
10) Corporation stops.
a. Corporation stops shall have AWWA tapered threaded inlet and compression joint outlet connection for copper service pipe.
b. All metal parts of the stop assembly shall be made of bronze.
c. The stop shall be operated with a tee head and shall open when turned counterclockwise.
d. Corporation stops for copper service line pipe outlets shall be Ford FB1000 or alternate acceptable to the city.
11) Electric conductive wire.
a. Where PVC pipe is allowed to be installed, electric conductive wire shall be placed in the trench one foot above the pipe.
b. The tracer wire shall be 12-gauge, plastic coated copper wire suitable for this purpose.
c. Foil tape will not be acceptable.
12) Meter boxes for single-family residential (subdivisions).
a. Meter boxes shall be manufactured by Star Pipe Products or alternate acceptable to the city and shall be of cast iron, oval shape and have minimum inside dimensions of 19 inches by ten inches and shall be at least 11½ inches deep.
b. Lids shall fit snugly. Lids shall be banded together with a steel strapping and painted with black asphaltic paint before shipping.
c. The combined weight of the box and lid shall be not less than 60 pounds.
d. The lid shall be of cast iron and shall be designed to rest firmly on the seat inside the box and over-hang to prevent dirt from falling into the seat.
e. The lid shall be easily removed and replaced.
13) Service saddles—Double strapped.
a. Double strapped service saddles are required for services two and one-half inches and smaller in diameter and shall be Ford F202 double strap clamps suitable for use with ductile iron or PVC pipe or alternate acceptable to the city. See subsection D.5 above regarding the requirements for four-inch and larger diameter taps.
b. If a three-inch meter is used for the development, the developer must install four-inch DIP from the main to the meter, and then utilize a four-inch by three-inch reducer at the meter.
c. The city will not accept three-inch service material.
14) Meters and backflow preventers.
a. All meters two inches and smaller will be installed by the city in boxes located at the edge of the right-of-way. All meters three inches and larger will be installed by the developer under the supervision of the city engineer. All meters three inches and larger shall be in vaults located at the edge of the street right-of-way or proper easement shall be provided. No meter will be set until the meter set fee is paid and a building permit issued for the lot requesting service. Services shall be sized and located as shown in detail W724 "Water Line Maintenance Sign" (see chapter 112). All meters must register in gallons and programmed to read in thousand gallon units.
b. Except as elsewhere provided, all meters, service connections, and other equipment furnished by or for the city shall be and remain the property of the city. The city will, at its own expense, make routine tests of meters when it considers such tests.
c. All meters must be installed with at least five times the pipe diameter of straight pipe the same size as meter on the inlet and outlet side to permit proper calibration.
d. All three-inch and larger meters shall be a Neptune T-10 with E-Coder Register.
e. Each register shall compatible with the city's meter reading equipment.
f. All meter installed inside vaults must be level parallel, vertical, and horizontal to the meter vault.
g. A Number 57 stone gravel bed (four-feet minimum) or a positive drain shall be required underneath all vaults for drainage. All bedding must be level for proper functioning of the meter.
h. Stand-on pipe supports are required underneath the meter and wheel valves for support of the weight.
i. All openings or holes in the vault will be required to be enclosed with concrete and made water tight.
15) Polyethylene tubing for ductile iron pipe.
a. Where required by the city, polyethylene encasement tubing shall be manufactured of virgin polyethylene material conforming to the requirements specified in AWWA C105, section 4.1.1 for linear, low density polyethylene film.
b. The polyethylene film shall have a minimum thickness of eight mil.
c. Black polywrap shall be used for water mains and green polywrap shall be used for sewer force mains.
16) Valve markers.
a. One concrete valve marker shall be furnished and set at each line valve.
b. The marker shall be made of 3,000 PSI concrete, and shall be four feet long and four inches on each side, with two #3 reinforcing bars as shown on the detailed drawings.
c. The markers shall be set an even number of feet between the center line of the valve and the center line of the aluminum disc in the top of the marker, and the distance in feet between the valve and marker shall be stamped in the marker at the time of setting.
17) Valve box collars.
a. Each valve box shall have a concrete collar. These collars must be a minimum of three and one-half inches thick. They shall be square and sized 24 inches by 24 inches.
b. Precast collars may be used, provided that they are grouted in place to the valve box.
c. The box is to be flush with or a maximum of one inch above the finished grade.
d. The edge of the valve box is to be one-half inch above the edge of the concrete collar.
18) Concrete for thrust blocks and thrust collars. Concrete for thrust blocks and thrust collars shall have a minimum compressive strength of 3,000 PSI at 28 days.
19) Subgrade stabilizer stone. Stabilizer for subgrade shall be either approved crushed stone or gravel, uniformly graded from one-quarter inch to three-quarter inch in size.
20) Retainer glands. Retainer glands for mechanical joints shall be EBAAMega-Lug or alternate acceptable to the city.
21) Locked fire hydrant tee and adapter. Locked fire hydrant tees and adapters (anchor coupling) shall be submitted to the city for approval.
22) "Fast-Grip" gaskets. Inside of all casings and wherever else required by the city, DIP water main joints shall be slip joint restrained by using American Pipe "Fast-Grip" gaskets, U. S.
Pipe "Field-Lok" gaskets or alternate acceptable to the city.
23) Nitrile (NBR) gaskets. In areas where underground fuel storage tanks are located or are known to have been located and as directed by the city, the DIP water main joints shall use American Pipe "Nitrile (NBR)" (Acrylonitrile Butadiene) gaskets or alternate acceptable to the city.
Historia
(Ord. No. 2014-18, § 2, 8-21-2014; Ord. No. 2022-0317-01, 3-17-2022)