Canton · Ordenanza de zonificación
Part III - DEVELOPMENT CODE / Chapter 114 / Article III - CONSTRUCTION STANDARDS
Sec. 114-131. Backflow prevention.
Sobre este texto
- As published by Municode, retrieved 2026-11-11
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
(a) Required. All wastewater treatment plants, commercial businesses, industries, or institutions shall be required to install backflow prevention mechanisms. Additionally, approved backflow preventers or vacuum breakers shall be installed with all plumbing fixtures or equipment for which the potable water supply outlet may be submerged without the protection of a minimum air gap. The particular backflow prevention devices utilized in any given situation shall be as specified in the plumbing code or as approved by the water and sewer department manager.
(b) Minimum required air gap. The minimum required air gap shall be measured vertically from the lowest end of a potable water outlet to the flood rim or line of the fixture or receptacle into which it discharges. The minimum required air gap shall be twice the effective opening of a potable water outlet unless the outlet is a distance less than three times the effective opening away from a wall or similar vertical surface in which cases the minimum required air gap shall be three times the effective opening of the outlet. In no case shall the minimum required air gap be less than is provided in the plumbing code.
Historia
(Ord. No. 2017-0921-01, § 1, 9-21-2017)
Leer este código donde se publica (Municode) La fuente es el código de la ciudad tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.