Sec. 114-138. Fire service metering requirements.
Sobre este texto
- As published by Municode, retrieved 2026-11-11
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
(a) All fire service systems on private property having fire hydrants, hand hose connections, or sprinkler heads shall utilize underwriter approved full flow factory mutual fire line meters or shall be provided with dual service consisting of a separate domestic service meter and a detector meter on the fire service line.
(b) When unauthorized water is used through a detector meter or a dual service connection in three or more billing periods in one calendar year, it shall be replaced with a factory mutual full flow fire line meter. Unauthorized use of water is defined as non-fire-fighting water and/or water use without prior notification and approval of the city water system.
(c) All water meters, detector or fire line, shall be installed on or near city right-of-way.
(d) Vaults shall be constructed to city specifications.
(e) Vault construction and meter installation shall be inspected by the city after work has been completed to insure that specifications have been met.
Historia
(Ord. No. 2017-0921-01, § 1, 9-21-2017)