10.4.4. Technology park sound ordinance. In

Sobre este texto

  • As published by Municode, retrieved 2026-11-11
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

order to ensure that data centers do not contribute to noise pollution within the City, all data centers will be subject to the following standards:

A. Data center operations shall not produce continuous sound that exceeds an average of sixty-five (65) decibels over any 30-minute period from 8 a.m. to 6 p.m.,

measured at any adjacent property boundary between the data center site and a residential property. Nor shall data center

operations produce continuous sound that exceeds an average of fifty-five (55) decibels over any thirty-minute period from 6 p.m. to 8 a.m., measured at any adjacent property boundary between the site and residential property. Violations of these sound levels may be prosecuted in the same manner as other zoning ordinance violations.

B. After issuance of the certificate of occupancy for each data center building, the city may obtain sound studies or require the data center operator to provide a sound study to verify that the operation is in compliance with the requirements of paragraph A above. If a data center is found to be in violation of the

requirements of paragraph A above, the city may issue a notice of violation, which may direct that the data center take appropriate steps to operate within the requirements of paragraph A above. The zoning administrator may require the data center operator to propose a solution, and a time period for implementation. If the zoning administrator approves such a solution, and the data center fails

to successfully implement that solution within the time approved, the violator shall be subject to a fine up to one thousand dollars ($1,000.00) for each day that the violation exists until full compliance is obtained.

C. The data center operator shall continue to bear the costs of any sound test or study required to monitor violations in paragraph B.