Ir al contenido
Georgia Commons
Menú

Dunwoody · Ordenanza de zonificación

Appendix A - EXPIRED AND OBSOLETE ZONING DISTRICTS / Chapter 32 - UTILITIES / Article IV - SEWERS AND SEWAGE DISPOSAL / Division 6 - FATS, OILS AND GREASES

Sec. 32-368. FOG interceptor physical specifications/requirements.

Sobre este texto

  • As published by Municode, current through 2020-02-10
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

(a) All interior FOG interceptors shall:

(1) Be a minimum of 100 pounds in capacity as defined by the Plumbing Drainage Institute;

(2) Be made of corrosion-resistant coated metal;

(3) Be properly sized based on the results of an inspection and FOG evaluation;

(4) Contain properly installed and functioning baffle walls and other flow control devices necessary to achieve the appropriate retention time;

(5) Have at least a 30-minute interior retention time before gray water is discharged into the sewer system;

(6) Tie all of the fresh air fixtures to the FOG interceptor;

(7) Have a 15-foot distance between the FOG interceptor and the last fresh air fixture and have a proper flow control device;

(8) Have a temperature of discharge entering the interior FOG interceptor that does not exceed 140 degrees Fahrenheit; and

(9) Be Plumbing Drainage Institute rated, be accessible for inspection, and be installed in accordance with the manufacturer's specifications by a licensed plumber and not a representative and/or an apprentice of the licensed plumber.

(b) All exterior FOG interceptors shall:

(1) Be a minimum of 1,000 gallons in capacity;

(2) Be properly sized based on the results of an inspection and FOG evaluation;

(3) Be constructed of reenforced materials suitable for load bearing and watertight to prevent inflow and infiltration;

(4) Be precast with a minimum of 3,000 psi concrete per applicable American Society for Testing and Materials standards with four to seven percent air entrapment;

(5) Have an invert elevation of the inlet between three inches to six inches above the invert elevation of the outlet;

(6) Contain a properly installed and functioning baffle wall and other flow control devices necessary to achieve an adequate time for FOG to properly separate but not to exceed 24 hours;

(7) Contain inlet and outlet T's made of schedule 40 PVC piping and at a 90- degree angle with a minimum diameter of the inlet and outlet piping to be six inches;

(8) Include the outlet T six inches from the manhole cover;

(9) Include T piping of the inlet and outlet that is within 18 inches of the bottom and at least five inches above the static liquid level of the tank;

(10) Have the FOG interceptor set level on a consolidated, stable base so that no settling or tipping of the FOG interceptor can occur;

(11) Connect all of the fresh-air fixtures to the FOG interceptor;

(12) Have the outlet discharge line from the FOG interceptor directly connected to a sewer line tapped into the collection main;

(13) Have solid manhole covers to prevent inflow and infiltration;

(14) Have two or more manholes for entry to each chamber of hydraulic liquid mass;

(15) Be accessible for inspections and have no permanent or temporary structure or container placed directly over the FOG interceptor or installed in areas subject to traffic; and

(16) Be installed by a licensed plumber.

(c) The contents of any fryer oil containers shall not be mixed with any other FOG interceptor waste or any other nontoxic or toxic substances.

Historia

La línea de historia que la fuente imprime al final de la sección.

(Comp. Ords. 2008, ch. 25, art. III, div. 5.1, § 7)

Leer este código donde se publica (Municode) La fuente es el código de la ciudad tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.

Versión local-code:dunwoody/zoning/32-368@2020-02-10-920b392011

El asistente puede decir lo que dice esta sección en esta edición, citándola y enlazándola. No aplicará la ley a su situación, y nada de esto es asesoría legal.

Dunwoody Zoning Ordinance, Sec. 32-368. FOG interceptor physical specifications/requirements | Georgia Commons