Hawkinsville · Ordenanza de zonificación
Appendix A - UNIFIED LAND DEVELOPMENT REGULATIONS / Article IV - DEVELOPMENT DESIGN STANDARDS / Division 6 - STORM DRAINAGE
Sec. 4.6.2. Street cross drains.
Sobre este texto
- As published by Municode, retrieved 2026-11-11
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
a. Pipe size for culverts under streets (street cross drains) shall be determined by design runoff and hydraulic capacity. The minimum allowable street cross drain diameter shall be eighteen (18) inches, with a minimum slope of one percent.
b. Street cross drains shall be constructed of Class III reinforced concrete, corrugated aluminum, or bituminous coated corrugated steel. The least expensive materials shall be permitted unless site or other conditions identified by a Professional Engineer dictate otherwise.
c. Street cross drains shall be sized to carry at least the 10-year frequency storm. Cross drains shall be designed to pass the peak rate of discharge associated with a 100-year storm with at least one foot of freeboard from the top of the roadway shoulder.
d. Velocity at design flow shall be at least two (2) feet per second but not more than the velocity that would cause erosion damage to the conduit.
e. Street cross drain design is to be in accordance with the methods contained in the Georgia Department of Transportation's Drainage Manual for Highways, latest edition.
f. Street cross drains carrying live streams shall extend to where the crown of the pipe intersects the street slope.
Historia
(Ord. of 5-10-96)