Sec. 38-304. Storm sewer system materials.

Sobre este texto

  • As published by Municode, current through 2026-06-23
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

All materials shall typically conform to the following specifications:

(1) Concrete pipe.

a. The basic specification for concrete pipe is 18 inches and over, ASTM C 76, reinforced concrete pipe furnished in not less than eight-foot lengths.

b. Each length or joint of concrete pipe shall have been stamped at the plant of manufacture showing strength or reinforcement class, wall thickness designation, date of manufacture and manufacture symbol.

c. Joints. Fill the annular space with grout and inside of each joint shall be wiped smooth. Use grout mixture consisting of not more than five gallons of water per sack of cement. Utilize cement conforming to AASHTO M85 or M150.

(2) Elliptical concrete pipe.

a. Basic specification: ASTM C 507, reinforced, elliptical sewer pipe furnished in not less than eight-foot lengths.

b. Maximum absorption by standard ASTM test may not exceed seven percent and pipe must be aged at manufacturing plant for not less than five days.

c. Identification: Stamp each length or joint of elliptical concrete pipe at the plant of manufacture showing strength or reinforcement class, wall thickness designation, date of manufacture, manufacturer's symbol and quadrant reinforcing symbol.

d. Joints: Use one of the following jointing systems. Once a system is selected it shall be utilized for the entire project unless specified or authorized otherwise.

1. Cement grout type which results in entire joint annular space being filled with grout and inside of each joint being wiped smooth. Use grout mixture consisting of not more than five gallons of water per sack of cement. Utilize cement conforming to AASHTO M85 or M150.

2. Preformed flexible pipe joint compound to be confined in the tongue and groove joint meeting federal specification SS-S-00210.

3. Corrugated plastic pipe. Corrugated, flexible conduit with slip-on joints made of polyethylene conforming with ASTM F405 and F449.

4. Bituminous coated corrugated aluminum pipe.

i. Basic specification: AASHTO M196 with full uniform bituminous coating having minimum thickness of 0.05 inch and conforming with

AASHTO M190.

ii. Joints: Fully bituminous coated coupling bands manufactured from base metal as pipe. Utilize bands of same manufacturer as pipe.

iii. Pipe fittings: Use standard, factory fabricated adapters, wyes, tees, and other necessary fittings comparable to pipe with which connected.

(3) Coarse granular material for pipe bedding.

a. Crushed stone, crushed gravel or natural gravel meeting ASTM C33, and having No. 67 gradation (3

/4 to No. 4 sieve).

b. Fine granular material for pipe bedding shall be uniformly graded, natural or manufactured sand composed of hard, durable particles with 100 percent passing a No. 4 sieve, not more than 25 percent passing a No. 100 sieve and containing no more than 25 percent total of silt and clay.

(4) Miscellaneous materials.

a. Clay brick: ASTM C32, grade MS or ASTM C32 sewer and manhole brick or ASTM C216 facing brick. Grade MW or SW, of nominal size8×2- 1 /4 ×3- 3

/4 inches, select color and texture.

b. Concrete block: ASTM C55, grade P-II of nominal size8×2- 1 /4 ×3- 3

/4 inches, gray-white concrete color with smoothed formed natural texture.

c. Rubble stone: Provide stone not less than six inches thick and 12 inches wide and of proper shape to bring masonry structures to true lines, shapes and elevations.

Smaller stones may be used to fill interior of walls. Provide stone free of rounded, worn, weathered and scarred surfaces, and also free of segregation, seam, cracks, pyrite intrusions and other defects tending to reduce weather resistance.

(5) Precast concrete drainage structures.

a. Use precast, concrete drainage structures, including precast concrete pipe sections, flared end sections, adjustment rings, tapered sections, drop inlets, manholes, and other related products which conform to the requirements of ASTM C478 and/or C789. Furnish structure having a minimum wall thickness of four inches or one-twelfth the interior diameter, whichever is greater. Accurately cast openings to meet specific project requirements.

(6) Structure steps.

a. Use steps conforming with applicable government safety regulations and the requirements stated below.

b. Provide individual steps, mortared or cast into walls, and conical tops of all manholes and similar structures. Align steps so as to form a continuous ladder with steps equally spaced vertically, no more than 16 inches apart, using steps having a minimum length of ten inches and which project a minimum clear distance of four inches from the wall. Use steps designed to prevent the foot from sliding off the end, and whose exposed parts are free of any hazardous, sharp edges, burrs or projections.

c. Steps, fastenings and installation must be capable of supporting a single, concentrated load of 300 pounds. Use designs based on imposed loads being concentrated at such points as will cause maximum stresses in the structural element being considered.

d. Plastic coated steel meeting the requirements of ASTM C478, D1246 and A615 grade 60.

(7) Metal castings.

a. Provide castings of uniform quality, free from blowholes, porosity, hard spots, shrinkage, distortion or other significant defects, and having smooth surfaces free of casting sand, fins and burrs. Use component parts which fit together uniformly, in a secure fashion. Where castings have lids or covers, make provisions for a non-rocking fit. Use gray iron castings meeting the ASTM A38, class 30 specification. Shop paint all casting surfaces with not less than one coat of asphaltic paint.

(8) Mortar materials.

a. Cement: Portland cement ASTM C150, type I or II.

b. Sand: ASTM C144.

c. Water: Clean, fresh, free from oil, acid, organic material and other detrimental substances.

(9) Additional specification for storm sewer.

a. Precast concrete units:

1. Set precast units plumb and to exact grade on approximately three inches of compacted sand bedding.

2. In the event field conditions necessitate additional pipe connections for which no holes have been cast, neatly chip necessary holes, being careful not to crack portions of unit to remain. Replace any units excessively damaged as a result of field modification.

3. For storm sewer units constructed of more than one precast element, fill all joints solidly with mortar. Use mortar or concrete to seal joints between units and connecting pipe.

b. Masonry structures:

1. Examine masonry units before installation and reject all units which are cracked, damaged or in any way fail to meet the requirements of this chapter.

2. Set masonry units in full mortar bed, carefully fit units around pipe openings, etc., so as to fill all voids. Completely fill any remaining voids with mortar. Do not use mortar which has been mixed more than 45 minutes or which has been retempered.

3. When using multi-wythe construction, make every fifth coarse a header coarse.

4. Do not install masonry when air temperature is below 40 degrees Fahrenheit and falling.

5. Do not backfill against masonry structures until they are at least seven days old. In cold weather delay backfilling for a longer time to allow additional curing time for mortar.

c. Metal castings:

1. Examine each casting before installation and reject all castings which are cracked, damaged or in any other way fail to meet the specifications.

2. Clean castings of dirt, mud, grease . . . etc., before installation.

3. Set castings according to location and arrangement shown on the plan.

Rigidly support castings to maintain true alignment and elevation. Where castings are located in concrete or mortar construction, thoroughly work concrete or mortar around the casting so as to eliminate voids and provide sold bearing surfaces and rigid construction.

4. Make frames subject to traffic firm and stable under actual traffic conditions. When constructed in paved areas, set frames to conform with exact pavement surface including tilting frame where necessary to match pavement surface.

Historia

La línea de historia que la fuente imprime al final de la sección.

(Res. No. LD05-A049, 9-23-2005)