Ir al contenido
Georgia Commons
Menú

Leesburg · Ordenanza de zonificación

Appendix C - LAND DEVELOPMENT REGULATIONS / Article X - POTABLE WATER REQUIREMENTS / Division 1 - GENERALLY

Sec. 10.03. Water line design criteria.

Sobre este texto

  • As published by Municode, retrieved 2026-11-11
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

(a) Working pressure. All pipe, fittings, valves, fire hydrants and appurtenances shall be capable of full service at a working pressure of not less than 150 psi.

(b) Pressure. All water mains including those not designed to provide fire protection, shall be sized after hydraulic analysis to maintain a minimum, in service pressure of 20 psi at ground level under all conditions of design flow.

(c) Design flow.

(1) The design flow is to consist of projected demand plus fire flow (if required). To determine projected peak flow for residential developments the values in Table 6.3A shall be used. For developments other than residential, utilize AWWA Manual of Water Supply Practices M22, Sizing Water Service Lines and Meters, to establish peak demand. For fire flow, select the proper value from Table 6.3B.

(2) Any new water lines connected to a utilities authority water main with pressure supplied by an elevated tank shall be required to design for fire flow.

Table 6.3A Peak Water Demand for Residential Developments Number of Dwelling Units Gallons per Minute per Dwelling Unit 5 8.0 10 5.0 20 4.3 30 3.8 40 3.4 50 3.0 60 2.7 70 2.5 80 2.2 90 2.1 100 2.0 150 1.6 200 1.3 300 1.2 400 0.9 500 0.8 750 0.7 1,000 0.6 Table 6.3B Minimum Design Fire Flows Zoning District Gallons per Minute R-1 750 R-2 1,000 R-3 750 C-1 750 C-2 1,000 I-1 1,250 I-2 1,250

Leer este código donde se publica (Municode) La fuente es el código de la ciudad tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.

Versión local-code:leesburg/zoning/appendix-c-article-x-division-1-10.03@2026-11-11-38b6507499

El asistente puede decir lo que dice esta sección en esta edición, citándola y enlazándola. No aplicará la ley a su situación, y nada de esto es asesoría legal.

Leesburg Zoning Ordinance, Sec. 10.03 (Appendix C, Article X, Division 1). Water line design criteria | Georgia Commons