Part I - OFFICIAL CODE OF COBB COUNTY, GEORGIA / Chapter 54 - FIRE PREVENTION AND PROTECTION / Article VI - FIRE PROTECTION SPRINKLER SYSTEM REQUIREMENTS

Sec. 54-93. Fire protection sprinkler systems requirements.

Sobre este texto

  • As published by Municode, current through 2025-11-20
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

(a) Except as otherwise provided, supervised fire protection sprinkler systems shall be required for all new hotels and dormitories as described in this subsection and shall be required for existing hotels and dormitories as described in section 54-94. NFPA 13R sprinkler systems shall be allowed in structures up to and including four stories in height. All buildings over four stories in height shall be protected by a NFPA 13 sprinkler system.

(b) Except as otherwise provided, supervised fire protection sprinkler systems shall be required for all new apartment buildings two stories or more in height. NFPA 13R sprinkler systems shall be allowed in structures up to and including four stories in height. All buildings over four stories in height shall be protected by a NFPA 13 sprinkler system. All balconies and storage closets accessed from the balcony shall be protected by the fire protection sprinkler system.

(c) Exception: Fire protection sprinkler systems are not required for new single story hotels, dormitories and apartment buildings with exit doors leading directly outside from each dwelling unit.

(d) All existing hotels, dormitories, and apartment buildings that undergo a substantial renovation, as defined in section 54-54(i).

(e) Except as otherwise provided, all new board and care occupancies (personal care homes) with four or more clients and all community living arrangements shall be equipped with an approved sprinkler system.

(f) Sections 903.3.1.2.1, 903.4, 903.4.1, 903.4.2, and 903.4.3 of the International Fire Code adopted in section 54-52 are adopted for enforcement on new installations and buildings that undergo substantial renovation or a change in the classification of occupancy.

(Ord. of 2-27-07; Ord. of 7-24-07; Amd. of 2-24-09;

Amd. of 2-26-13; Amd. of 2-23-16; Amd. of 11-20-25)

Reuniones que se refieren a esta sección

Encontradas: 1. Son reuniones de este gobierno cuyas actas o transcripciones automáticas nombran esta sección, o una ordenanza de su línea de historia, de la más reciente a la más antigua. Halladas por regla a partir de las propias palabras de esos registros. Una referencia es un enlace a otro registro, no una afirmación de que la sección se aplica o se cambió.

Leer este código donde se publica (Municode) La fuente es el código del condado tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.

Versión local-code:cobb-county/code/54-93@2025-11-20-8b66ed7d0e

El asistente puede decir lo que dice esta sección en esta edición, citándola y enlazándola. No aplicará la ley a su situación, y nada de esto es asesoría legal.