Part II - CODE OF ORDINANCES / Chapter 8 - BUILDINGS AND BUILDING REGULATIONS / Article V - PLUMBING / Division 3 - HIGH EFFICIENCY FIXTURES
Sec. 8-206. Water closets and toilets.
Sobre este texto
- As published by Municode, current through 2024-07-09
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
After July 1, 2012, the following shall be required for water closets and toilets:
(1) Dual flush. Dual flush water closets and toilets must meet the following standards:
a. The average flush volume of two reduced flushes and one full flush may not exceed 1.28 gallons;
b. The toilet meets the performance, testing, and labeling requirements prescribed by the following standards, as applicable:
1. American Society of Mechanical Engineers Standard A112.19.2-2008;
2. American Society of Mechanical Engineers Standard A112.19.14-2006 Six-Liter Water Closets Equipped with a Dual Flushing Device"; and
3. Is listed to the WaterSense Tank-Type High Efficiency Toilet Specification; or
(2) Single flush. Single flush water closets, including gravity, pressure assisted, and electro-hydraulic tank types, must meet the following standards:
a. The average flush volume may not exceed 1.28 gallons;
b. The toilet must meet the performance, testing, and labeling requirements prescribed by the American Society of Mechanical Engineers Standard
A112.192/CSA B45.1 or A112.19.14; and
c. The toilet must be listed to the WaterSense Tank-Type High Efficiency Toilet Specification.