Sec. 42-50. Static pile protection.

Sobre este texto

  • As published by Municode, retrieved 2026-11-23
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

(a) Interior pile temperatures of piles subject to this ordinance shall be monitored and recorded on a regular basis per the operational plan. Internal pile temperatures must be taken at 2/3 the pile height, 12 to 24 inches from the surface with a probe-type thermometer.

Readings shall be made at not greater than 50-foot intervals along the length of the pile.

(b) Once windrows exceed 158 F°, the operator must institute reasonable measures to prevent internal temperatures from continuing to rise.

(c) Once windrows exceed 170 F°, the windrows must be reduced in size, be rotated, and be monitored daily until temperatures drop below 158 degrees F°. All green waste stockpiles shall be re-mixed as necessary to alleviate any fire due to spontaneous combustion or temperatures above 170 F°.

(d) Windrows shall be visually inspected on a weekly basis. Once fires have been detected in any windrows at a site, this visual inspection shall be a minimum daily requirement.

Daily inspections shall continue until the threat of fire no longer exists, and the director approves suspension.

(e) All temperature and pile-handling records shall be kept on file at the site and be made available for inspection by department personnel. Data shall include date, time, temperature, specific location, and person conducting measurement.

Historia

La línea de historia que la fuente imprime al final de la sección.

(Ord. of 3-28-2017, § 1)

Leer este código donde se publica (Municode) La fuente es el código del condado tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.

Versión local-code:barrow-county/code/42-50@2026-11-23-6d006a3a53

El asistente puede decir lo que dice esta sección en esta edición, citándola y enlazándola. No aplicará la ley a su situación, y nada de esto es asesoría legal.

Barrow County Code of Ordinances, Sec. 42-50. Static pile protection | Georgia Commons